Plan Review Notes
Plan Review Notes For Permit 02101739
Permit Number 02101739
Review Stop P
Sequence Number 2
Notes
Date Text
2003-02-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: SHT A5 PLEASE
 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS FOR BOTH THE OLD
 AND THE NEW ROOFS. (NEW PARPET HEIGHT
 EFFECTS BOTH ROOFS). SHOW SQUARE FOOTAGE
 FOR ALL ROOFS INCLUDING 1/2 AREA OF ALL
 VERITCAL WALLS AND ANY AREA OF ROOFS
 THAT DRAIN ONTO THE FOOFS FROM ABOVE.
 SEE SECTIONS 1106 & 1107.
 2) WILL THIS BE AN ASSISTED LIVING
 RESIDENCE?
 3) ALL BATHROOMS SHALL COMPLY WITH
 CHAPTER 11 OF THE FBC-2001.
 4) WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377