Plan Review Notes For Permit 02101739
Permit Number 02101739
Review Stop M
Sequence Number 2
Notes
Date Text
2003-02-18 00:00:00DENIED:
  
 1.PLAN SHEET A(B)3 DETAIL 9, INDICATES
 TENANT SEPARATION.CLARIFY FIRE
 RESISTANCE RATING FOR THIS PARTITION.
 SHOULD RATING BE 1 HR OR GREATER, FIRE
 DAMPERS ARE REQUIRED AT EACH PENETRATION
 AS PER 2001 FBC(M) 607.2.1.
  
 2.AS PER 2001 FBC CHAPTER 13 SECTION
 407.1.ABCD.2.2.2 ZONES, HEATING AND
 COOLING TO EACH ZONE SHALL BE CONTROLLED
 BY INDIVIDUAL THERMOSTATIC CONTROLS
 RESPONDING TO TEMPERATURE WITHIN THE
 ZONE.A DWELLING UNIT IS CONSIDERED A
 ZONE.
  
 3.PROVIDE INFORMATION ON THE KITCHEN.
 INDICATE ANY NEW EQUIPMENT.SEPARATE
 PLANS & PERMIT REQUIRED FOR HOOD & FIRE
 SUPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.