2002-11-19 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 34
 FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) PLANS DO NOT HAVE SUFFICENT CLAIRITY
 AND DETAIL TO INDICATE THE NATURE AND
 CHARACTER OF THE WORK BEING DONE. PLANS
 ARE SMUGED AND HARD TO READ. PLEASE SUB-
 MIT PLANS THAT ARE CLEAR AND READABLE.
 SEC 104.2.1
 2) SHT A2 APPLICABLE CODES ARE FBC-2001
 NOT AS STATED ON PLANS.
 3) SHT A5 PLEASE SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY DRAINS FOR BOTH
 THE OLD AND NEW ROOFS. (NEW PARAPET
 HEIGHT EFFECTS BOTH ROOFS). SHOW SQUARE
 FOOTAGE FOR ALL ROOFS INCLUDING 1/2 AREA
 OF ALL VERTICAL ROOFS AND ANY AREA OF
 ROOFS THAT DRAIN ONTO ROOFS FROM ABOVE.
 SECTION 1106 & 1107
 4) PLEASE INDICATE THE NUMBER OF OCCU-
 PANTS TO BE HOUSED AT THE FACILITY AND
 SUBMIT CALCULATIONS FOR PLUMBING FACIL-
 ITIES REQUIRED. SECTION 434.4.5.1.
 5) PLEASE SUBMIT AN EXISTING FLOOR PLAN
 TO DETERMINE EXISTING FACILITIES.
 6) SHT EP1 PLUMBING NOTES #7, AIR CHAMB-
 ERS ARE NOT APPROVED. DELETE REFERENCE.
 7) PLEASE SUBMIT DETAILS FOR BATHROOMS
 PER SECTION 434.4.5.3. SHOW ALL GRAB
 BARS REQUIRED FOR SHOWERS OR TUBS AND
 FOR WATER CLOSETS.
 8) SECTION 434.4.3.1 REQUIRES A MINIMUM
 LIVING & DINING SPACE OF 35 SQ FT PER
 RESIDENT, LIVE IN STAFF, & LIVE IN FAM-
 ILY MENBERS. PLEASE INDICATE ON PLANS.
  
 REVIEW BY KEN STEVENS