2002-11-05 00:00:00 | *************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE PLANS SIGNED AND | | SEALED BY AN ENGINEER MUST CONTAIN | | A TITLE BLOCK W/ INFORMATION SET FORTH | | IN FAC. 61G15-23.002 | | | | 2)NOTE: PLEASE SHOE ALL CIRCITING ON | | PLANS AND CORRELATE WITH PANEL SCHEDULE- | | (S). | | | | 3)NOTE: PLEASE NOTE, SD`S REQ`D INSIDE | | AND OUTSIDE ALL SLEEPING ROOMS AND A | | MIN OF 3' AWAY FORM BATHROOMS. | | NFPA-72 8-1.4.1.6 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE NAY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|