2002-12-04 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) 61G15-23.002(2) FL. ADMIN. CODE. |
| PLANS SIGNED AND SEALED BY A |
| PROFESSIONAL ENGINEER SHALL INCLUDE THE |
| NAME AND ADDRESS OF THE ENGINEER AS WELL |
| AS THE NAME, ADDRESS AND CERTIFICATE OF |
| AUTHORIZATION NUMBER FOR THE ENGINEERING |
| BUSINESS, IF APPROPRIATE. |
| |
| 4) FBC 309, 420, 434.IS THE OCCUPANCY |
| GROUP I (UNRESTRAINED) INSTITUTIONAL, |
| R4 ASSISTED LIVING FACILITY OR NURSING |
| HOME?THE PLANS AND/OR APPLICATION FORM |
| SHALL STATE WHICH OCCUPANCY CATEGORY THE |
| FACILITY WILL BE USED FOR.UNTIL THIS |
| INFORMATION IS PROVIDED, A FULL PLAN |
| REVIEW CANNOT BE COMPLETED. |
| |
| 5) FBC* 104.2.1.3SHEETS A1, A2, A3 AND |
| A6 HAVE TEXT WHICH CANNOT BE READ DUE TO |
| POOR CONTRAST/COPY QUALITY.SUBMIT |
| LEGIBLE COPIES.A FULL PLAN REVIEW HAS |
| NOT BEEN COMPLETED. |
| |
| 6) FBC 11-4.1.5ACCESSIBLE TOILETS AND |
| BEDROOMS.THE EXTENT OF REQUIRED |
| PROVISIONS WILL BE DEPENDENT UPON THE |
| RESPONSE TO COMMENT 4 ABOVE. |
| |
| 7) FBC 104.2.1.2THE PLANS SHALL STATE |
| THE FLOOR AREA AND, IF DIFFERENT, THE |
| 'AREA UNDER ROOF' FOR THE EXISTING AND |
| THE NEW CONSTRUCTION. |
| |
| 8) SHEET A3, GENERAL NOTES.THE FIRST |
| NOTE REFERS TO THE CODE "..AS AMENDED BY |
| PALM BEACH COUNTY".THIS SHOULD READ |
| "..AS AMENDED BY THE CITY OF WEST PALM |
| BEACH".THE FIFTH NOTE REFERS TO THE |
| STANDARD BUILDING CODE AND PALM BEACH |
| COUNTY AGAIN.ALL SUCH REFERENCES SHALL |
| BE AMENDED. |
| |
| 9) SHEET A3, GENERAL STRUCTURAL NOTES. |
| NOTE 1 SHALL BE AMENDED TO REFERENCE |
| FLORIDA BUILDING CODE AND THE CITY OF |
| WEST PALM BEACH INSTEAD OF STANDARD |
| BUILDING CODE AND PALM BEACH COUNTY. |
| |
| 10) SHEET A3, TRUSS CONNECTOR/ANCHOR |
| SCHEDULE NOTES.THE NOTES ARE NOT FULLY |
| LEGIBLE BUT APPEAR TO MAKE REFERENCE TO |
| ASCE 7-88 AND A WIND SPEED OF 110 MPH. |
| THIS SHALL BE AMENDED TO ASCE 7-98 AND |
| 140 MPH.AMEND ALL OTHER REFERENCES TO |
| SOUTHERN BUILDING CODE, STANDARD |
| BUILDING CODE, 110 MPH WIND SPEED AND |
| ASCE 7-88, INCLUDING THE TWO OCCURANCES |
| IN THE LOAD SCHEDULE ON SHEET A3. |
| |
| 11) FBC 2405.2THE FOLLOWING GLAZING IS |
| IN A 'HAZARDOUS LOCATION' AND IS |
| REQUIRED TO BE SAFETY GLASS SATISFYING |
| THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| SAFETY COMMISSION 16, CODE OF FEDERAL |
| REGULATIONS, PART 1201 (CPSC 16-CFR, |
| PART 1201): |
| - SHOWER WINDOWS (SCHEDULE MARK C) |
| - ANY GLAZING IN THE SHOWER DOORS |
| SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE |
| |
| 12) FBC 1013.3 & FBC 11-4.8.2EXTERIOR |
| RAMPS TO THE NEW HALL AND THE NEW PATIO |
| HALL.SHEETS A2 AND S1 SHOW FIVE RISERS |
| WHICH IMPLIES A LEVEL CHANGE OF 34.75". |
| THE PROPOSED RAMP WOULD HAVE A SLOPE |
| GREATER THAN 1 IN 12.AMEND THE RAMP TO |
| COMPLY. |
| |
| 13) FBC 104.2.1.2EXTERIOR STAIR AT |
| NORTH ELEVATION.IS THIS STAIR NEW |
| CONSTRUCTION?SHEET A6 SHOWS IT AS PART |
| OF THE EXISTING BUILDING, AND IT IS NOT |
| SHOWN ON SHEET A1 AS PART OF THE NEW |
| CONSTRUCTION.IS THERE A RAMP |
| ASSOCIATED WITH THIS STAIR, NO DETAILS |
| HAVE BEEN PROVIDED?AMEND THE PLANS TO |
| CLARIFY THE PROPOSALS FOR THIS AREA. |
| |
| 14) THE SUBMITTED SHUTTER PRODUCT |
| APPROVAL NOA# 99-0318.03 EXPIRED PRIOR |
| TO THE DATE OF PERMIT APPLICATION. |
| SUBMIT AN NEW PRODUCT APPROVAL. |
| |
| 15) NORTH ELEVATION WINDOW (SCHEDULE |
| MARK B).THE SUBMITTED SINGLE HUNG |
| WINDOW PRODUCT APPROVAL NOA# 01-0226.04 |
| IS APPLICABLE TO SINGLE UNIT |
| APPLICATIONS ONLY (SEE LIMITATIONS ON |
| SPECIFIC CONDITIONS SHEET).SUBMIT A |
| NEW WINDOW PRODUCT APPROVAL OR AN |
| APPROPRIATE MULLION PRODUCT APPROVAL. |
| |
| 16) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| OLD SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHALL BE INCLUDED WITH THE |
| RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| ROBERT BROWN(561) 659 8096 EXT 8499 |