Plan Review Notes For Permit 02101632 |
Permit Number |
02101632 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-04-29 00:00:00 | ********** UNSAT ***** | | | | 1)NOTE: PLEASE CORRELATE RISER AND | | NOTE TO RISER. ONE SHOWS METER/MAIN | | COMBO W/ A 225A MCB AND RISER SHOWS | | 200A. | | | | 2)NOTE: PLEASE SEE MISSING KITCHEN | | COUNTERSPACE RECEPT PER 210-52C-1 | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected]. |
|