Plan Review Notes
Plan Review Notes For Permit 02101578
Permit Number 02101578
Review Stop P
Sequence Number 2
Notes
Date Text
2002-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 *****FROM PREVIOUS REVIEW
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 ********NEW COMMENT
 1) PLEASE VERIFY WITH GAS PROVIDER THE
 DELIVERY PRESSURE. THEY DO NOT USEA
 1LB METER AND IF IT IS A 1LB SYSTEM THEN
 ALL REGULATORS SHALL BE SHOWN ON GAS
 RISER DIAGRAM. MANUFACTURE CUT SHEETS
 FOR REGULATORS WILL BE REQUIRED, AND
 A SHUT OFF VALVE AND UNION SHALL BE
 SHOWN ON RISER.
 2) PLANS SHALL BE SUBMITTED AS COMPLETE
 SETS. ALL OLD SHEETS SHALL BE REMOVED,
 AND NEW SHEETS INSERTED. SUBMIT ON SET
 OF OLD SHEETS TAKEN OUT FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377