2002-11-07 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL CODE |
| FBC-2001 CHAPTER 11 |
| |
| 1) SHT A1.0 PLEASE SUBMIT CALCULATIONS |
| FOR MINIMUM FACILITIES PER TABLE 403.1. |
| INDICATE IF SEATING IS FIXED, NOT FIXED, |
| OR BOTH. NUMBER OF BOOTH SEATING. SEE |
| TABLE 1003.1 FBC-2001 BUILDING. |
| 2) SHT A2.0 SUBMIT MANUFACTURE INFORMAT- |
| ION FOR WATER FILTER FOR ICE MACHINE. |
| FILTER SHALL BE NSF APPROVED. |
| 3) SHT A4.1 WATER RISER DIAGRAM. WATER |
| HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| THE FIXTURE IN AN "EFFICTIVE RANGE" NOT |
| AT TOP OF DROPS PER MANUFACTURE INSTALL- |
| ATION AND PDI-WH 201. |
| 4) SHT A4.1 GAS RISER, FOLLOWING INFOR- |
| MATION REQUIRED FOR GAS PERMIT APPLICAT- |
| ION. (SEPARATE GAS PERMIT REQUIRED) |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2001 FUEL GAS CODE SEC |
| 502 THRU 506. |
| E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, & FBC-2001 |
| FUEL GAS CODE SEC. 402.2. |
| F. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| G. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| H. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. |
| |
| REVIEW BY KEN STEVENS |