Plan Review Notes
Plan Review Notes For Permit 02101578
Permit Number 02101578
Review Stop P
Sequence Number 1
Notes
Date Text
2002-11-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL CODE
 FBC-2001 CHAPTER 11
  
 1) SHT A1.0 PLEASE SUBMIT CALCULATIONS
 FOR MINIMUM FACILITIES PER TABLE 403.1.
 INDICATE IF SEATING IS FIXED, NOT FIXED,
 OR BOTH. NUMBER OF BOOTH SEATING. SEE
 TABLE 1003.1 FBC-2001 BUILDING.
 2) SHT A2.0 SUBMIT MANUFACTURE INFORMAT-
 ION FOR WATER FILTER FOR ICE MACHINE.
 FILTER SHALL BE NSF APPROVED.
 3) SHT A4.1 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFICTIVE RANGE" NOT
 AT TOP OF DROPS PER MANUFACTURE INSTALL-
 ATION AND PDI-WH 201.
 4) SHT A4.1 GAS RISER, FOLLOWING INFOR-
 MATION REQUIRED FOR GAS PERMIT APPLICAT-
 ION. (SEPARATE GAS PERMIT REQUIRED)
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE SEC
 502 THRU 506.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, & FBC-2001
 FUEL GAS CODE SEC. 402.2.
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  