Plan Review Notes For Permit 02101578 |
Permit Number |
02101578 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-15 00:00:00 | PROVISO: | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | FIRESUPRESSION, AND WALK-IN COOLER. | | PLEASE PROVIDE MANUFACTURER SUBMITTAL | | & INSTALLATION INSTRUCTIONS WITH PERMIT | | APPLICATION. | | | | HOOD SUBMITTAL - PROVIDE DETAIL OF | | GREASE DUCT (TERMINATION, SLOPE, ACCESS | | DOORS, ETC).SHOW COMPLIANCE WITH 2001 | | FBC(M) SECTION 507 & 507 AS WELL AS | | NFPA 96.PROVIDE AIR BALANCE.INDICATE | | AIR MAKE-UP FOR HOOD. | | | | PLEASE NOTE AHU PIPING DETAIL DIAGRAM - | | BULL-HEADING TEE IS NOT ALLOWED. | | 2001 FBC(M) 1206.1.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. | | NO MECHANICAL PLANS SUBMITTED FOR REVIEW |
|