Plan Review Notes
Plan Review Notes For Permit 02101578
Permit Number 02101578
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-05 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE ADD SHOW WINDOW RECEPTS
 FOR OTHER WINDOWS ALONG SIDE. 210-62
  
 2)NOTE: PLEASE CORRELATE PANEL "B" ON
 RISER AND PANEL DETAIL. ONE SHOWS MCB
 (REQ`D) AND OTHER SHOWN AS MLO.
  
 3)NOTE: PLEASE SHOW CONDUCTORS ON SECOND
 -ARY SIDE OF TRANSFORMER.
  
 4)NOTE: PLEASE PROVIDE LOAD CALCULATION
 ON EXSITING 100A MAIN FEEDING SPACE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.(215-5) IF THERE ARE ANY QUESTION
 -S, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372