2002-11-05 00:00:00THE DOORS SHOWN AS (7) OBSTRUCT THE REAR
 EXIT.SEE FBC 1012.1.4.PLEASE REVISE
 AS NECESSARY.
  
 IS THE DEMISING WALL AT THE WEST END NEW
 OR EXISTING?
  
 SHEET A1.2, SPECIFY THE CONNECTIONS FOR
 THE NEW STEEL COLUMNS TO THE STRUCTURE
 ABOVE AND SPECIFY THE WELDS.SEE FBC
 104.2
  
 SHOW THE DESIGN PRESSURES FOR THE NEW
 STORE FRONT.SEE FBC 1607.1.7.
  
 A1.2 THE WALL SECTIONS SHOW USE OF
 PLYWOOD IN THE EXTERIOR WALL.THIS IS
 PROHIBITTED IN TYPE IV CONSTRUCTION,
 SEE FBC 606.
  
 THE "HEAD DETAIL" ON SHEET A1.2 CALLS
 OUT PRE-CAST LINTEL.WHERE WILL THIS
 BE USED?
  
 SHEET A1.3 NOTES A STUCCO CEILING ON
 METAL CHANNELS.PROVIDE A SPECIFIC
 CONSTRUCTION DETAIL INCLUDING
 CONNECTIONS.SEE FBC 104.2.
  
 WHERE WILL THE KITCHEN HOOD EXHAUST?
 SHAFT DETAILS?
  
 PROVIDE A CONSTRUCTION DETAIL FOR THE
 DROPPED SOFFIT/BULKHEAD OVER THE
 KITCHEN AREA.
  
 THE DOOR SCHEDULE CALLS OUT A DEAD BOLT
 FOR DOOR #8.SEE FBC 1019.7.