Plan Review Notes For Permit 02101578 |
Permit Number |
02101578 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-05 00:00:00 | THE DOORS SHOWN AS (7) OBSTRUCT THE REAR | | EXIT.SEE FBC 1012.1.4.PLEASE REVISE | | AS NECESSARY. | | | | IS THE DEMISING WALL AT THE WEST END NEW | | OR EXISTING? | | | | SHEET A1.2, SPECIFY THE CONNECTIONS FOR | | THE NEW STEEL COLUMNS TO THE STRUCTURE | | ABOVE AND SPECIFY THE WELDS.SEE FBC | | 104.2 | | | | SHOW THE DESIGN PRESSURES FOR THE NEW | | STORE FRONT.SEE FBC 1607.1.7. | | | | A1.2 THE WALL SECTIONS SHOW USE OF | | PLYWOOD IN THE EXTERIOR WALL.THIS IS | | PROHIBITTED IN TYPE IV CONSTRUCTION, | | SEE FBC 606. | | | | THE "HEAD DETAIL" ON SHEET A1.2 CALLS | | OUT PRE-CAST LINTEL.WHERE WILL THIS | | BE USED? | | | | SHEET A1.3 NOTES A STUCCO CEILING ON | | METAL CHANNELS.PROVIDE A SPECIFIC | | CONSTRUCTION DETAIL INCLUDING | | CONNECTIONS.SEE FBC 104.2. | | | | WHERE WILL THE KITCHEN HOOD EXHAUST? | | SHAFT DETAILS? | | | | PROVIDE A CONSTRUCTION DETAIL FOR THE | | DROPPED SOFFIT/BULKHEAD OVER THE | | KITCHEN AREA. | | | | THE DOOR SCHEDULE CALLS OUT A DEAD BOLT | | FOR DOOR #8.SEE FBC 1019.7. |
|