2002-11-22 00:00:00 
  
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 02101310
 ADDRESS: 3753 VICTORIA RD
 CONT: M/I HOMES
 TELL # (561) 471-3440
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 ***BUILDING PROVISO***
  
 1) PLEASE ADDRESS HIGH SHEAR VALUE ON
 NAILS IN TRUSS ANCHOR SCHEDULE.
 A) HETA 20- (6)-10D= 1890
 B) TA16R-(6) 10DX 1 1/2=1000
 C) TAPR210(6) 10D= 1000
 THE VALUE OF THESE NAILS DEPENDS ON THE
 GAUGE AND TYPE OF NAIL (BRIGHT VS GAL),
 THE AVERAGE IS 112 LBS FOR A LIGHT GAUGE
 (18) TO 158 FOR A #3 GUAGE @ 158X6=948.
 THE COMMON 10D BRIGHT GAUGE IS #9, WITH
 A SHEAR VALU OF APPROX. 130 LBS FOR 6
 NAILS OR 780 LBS SHEAR.
  
 PLEASE COMMENT BEFORE ROOF FRAMING
 INSPECTION. SEE BOTH SIMPSON & USP
 CATOLOGS FOR ADDITIONAL INFO.
  
 FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SOILS REPORT TO THIS OFFICE BEFORE
 PLACEMENT OF CONCRETE FOR MONOLITHIC
 SLAB.
  
 BUILDING PLAN REVIEW