2002-10-22 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 02101251 |
| ADD: 4431 EMBARCADERO |
| CONT: MIKE MOORE |
| TEL: (561)775-3447 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) PLANS, SPECIFICATIONS,REPORTS OR |
| OTHER DOCUMENTS PREPARED BY THE DESIGN |
| PROFESSIONAL AND BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| FL ATATE STAT: 61G16.003 ARCHITECTS |
| |
| 3) THE LETTER FROM OLIVER & GLIDEN |
| INDICATES THAT THE EXISTING 1-HR RATED |
| CEILING GRID & TILE ARE TO BE REPLACED. |
| NO INFORMATION ON THE RATING OF THE GRID |
| NOR TILE HAS BEEN SUBMITTED. NEITHER IS |
| INFORMATION SUBMITTED ON THE LIGHT FIX- |
| TURES IF THE CANS ARE 1 HR RATED OR IF |
| RATED ENCLOSERES ARE TO BE USED. SEE |
| 705.1.1 FIRE RATED ASSEMBLIES, 705.6 FOR |
| PENETRATION OF HORIZONTAL ASSEMBLIES, |
| AND 705.6.2 MEMBRANE PENETRATIONS. |
| |
| 4)705.1.2 PENETRATIONS SHALL BE PRO- |
| TECTED BY AN APPROVED PENETRATION FIRE- |
| STOP SYSTEM AS TESTED IN ACCORDANCE WITH |
| ASTM E 814, WITH A MINIMUM POSITIVE |
| PRESSURE DIFFERENTIAL OF 0.01 INCH OF |
| WATER COLUMN AND AN F RATING OF NOT LESS |
| THAN REQUIRED RATING OF THE WALL |
| PENETRATED. INDICATE HOW CEILING TILE IS |
| TO BE HELD IN PLACE, ACCESS TO AREA |
| ABOVE THE CEILING, ETC? |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |
| FAX: (561)659-8026 |