Date Text
2003-03-28 00:00:00THE EXIT STAIRS FROM THE MEZZANINE ARE
 REQUIRED TO BE ENCLOSED IN FIRE RATED
 CONSTRUCTION IN ACCORDANCE WITH FBC
 1005.7.3.THE TRAVEL DISTANCE EXCEEDS
 75'.
  
 PORTAFAB PLANS SHEET 1 OF 3.WHAT ARE
 THE "SUPPORT BOARDS"
  
 WHAT ARE THE COLUMNS THAT SUPPORTS THE
 W10X39?INCLUDE THE CONNECTION AT THE
 BOTTOM.
  
 WHAT DO THE W10X15 BEAMS REST ON AT THE
 WALL ENDS?COLUMNS? THE VINYL AND
 PAPERWALL PANELS?
  
 WHAT IS THE DECKING SHOWN AS "DUST
 COVER"HOW IS IT FASTENED THE W10
 BEAMS?
  
 WHAT IS THE RISE AND RUN OF THE
 "U-SHAPED BOCA STAIR"?HANDRAIL
 DETAILS?LANDING CONSTRUCTION AND
 SUPPORT?DESIGN LOAD?
  
 ALSO, PLEASE PROVIDE A COPY OF THE
 STRUCTURAL CALCULATIONS DEMOSTRATING
 THE MEZZANINE CAN SUPPORT THE MINIMUM
 125 PSF LIVE LOAD.
  
 AS PREVIOUSLY NOTED IMPACT FEES MUST BE
 PAID TO THE COUNTY BEFORE A PERMIT MAY
 BE ISSUED.