2003-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW, SHT A2 SHOWER
 ROOM, SHOWER SHALL COMPLY WITH 11-4.21
 AND ALL SUBSECTIONS. PLEASE SHOW DETAILS
 ALSO ROOM SHALL REQUIRE A 5' TURNING
 RADIUS.
 2) SHT A2 TURNING RADIUS IS REQUIRED IN
 MEN'S TOILET ROOM, AND NOT REQUIRED IN
 STALL.
 3) FROM PREVIOUS REVIEW, SHT P-1 WATER
 ISOMETRIC, WATER HAMMER ARRESTORS REQD.
 IN SECTION 604.9 SHALL BE LOCATED NEAR
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING AT TOP OF DROP AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION INST.
 4) FROM PREVIOUS REVIEW, SHT P-1 WATER
 HEATER DETAIL, THERMAL EXPANSION CONTROL
 REQUIRED PER SECTION 607.3 & 607.3.2.
 5) FROM PREVIOUS REVIEW, SHT P-2 PLEASE
 SHOW LOCATION FOR SCUPPER DRAINS. SHOW
 SIZE OF EACH SCUPPER DRAIN AND SQUARE
 FOOTAGE BEING DRAIN THRU EACH SCUPPER.
 6) FROM PREVIOUS REVIEW, SHT P-3 MATER-
 IALS AND EQUIPMENT (L) & EXECUTION OF
 WORK (F) AIR CHAMBERS ARE NOT APPROVED.
 PLEASE DELETE REFERENCES>
  