Plan Review Notes For Permit 02101075 |
Permit Number |
02101075 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-01-31 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) FROM PREVIOUS REVIEW, SHT A2 SHOWER | | ROOM, SHOWER SHALL COMPLY WITH 11-4.21 | | AND ALL SUBSECTIONS. PLEASE SHOW DETAILS | | ALSO ROOM SHALL REQUIRE A 5' TURNING | | RADIUS. | | 2) SHT A2 TURNING RADIUS IS REQUIRED IN | | MEN'S TOILET ROOM, AND NOT REQUIRED IN | | STALL. | | 3) FROM PREVIOUS REVIEW, SHT P-1 WATER | | ISOMETRIC, WATER HAMMER ARRESTORS REQD. | | IN SECTION 604.9 SHALL BE LOCATED NEAR | | FIXTURES IN AN "EFFECTIVE RANGE" NOT IN | | THE CEILING AT TOP OF DROP AS SHOWN. | | PDI-WH 201 AND MANUF. INSTALLATION INST. | | 4) FROM PREVIOUS REVIEW, SHT P-1 WATER | | HEATER DETAIL, THERMAL EXPANSION CONTROL | | REQUIRED PER SECTION 607.3 & 607.3.2. | | 5) FROM PREVIOUS REVIEW, SHT P-2 PLEASE | | SHOW LOCATION FOR SCUPPER DRAINS. SHOW | | SIZE OF EACH SCUPPER DRAIN AND SQUARE | | FOOTAGE BEING DRAIN THRU EACH SCUPPER. | | 6) FROM PREVIOUS REVIEW, SHT P-3 MATER- | | IALS AND EQUIPMENT (L) & EXECUTION OF | | WORK (F) AIR CHAMBERS ARE NOT APPROVED. | | PLEASE DELETE REFERENCES> | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|