Plan Review Notes
Plan Review Notes For Permit 02101075
Permit Number 02101075
Review Stop E
Sequence Number 2
Notes
Date Text
2003-02-06 00:00:00************** UNSAT ***************
  
 PLEASE NOTE, SOME NOTES FROM
 FIRST REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE OCP FOR AHU`S 1&2,
 SHOWS 40A OCP FOR 10KW HEAT(MECH PLANS)
 PLEASE ADJUST AQND CORRELATE MECH AND
 ELECTRICAL PLANS. PLEASE ALSO SIZE OF
 OCP PER 424-3 IF AHU'S ARE INDEED 10KW
 AS SHOWN ON M SHEETS. PLEASE SEE LOADS
 SHOWN ON PANEL SCHEDULE, LOAD SHOWN
 EXCEEDS LOADS SHOWN ON LOAD CALCULATIONS
 FOR CHILLER/COND UNITS. THE HIGHER OF
 THE TWO LOADS NEED TO BE SHOWN IN LOAD
 CALCS. PLEASE RE-DO LOAD CALCULATIONS
 TO REFLECT LOADS OF AHU`S . SHOWN AT
 4.3 PER PHASE (CHILLERS AT 3.3 PER PHASE
 )??
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215-3,230-42 ETC.
  
 3)NOTE: PLEASE PLACE NOTE ON E-2,
 "NO HAZARDOUS MATERIALS TO BE USED AND
 DOES NOT MEET ANY LOCATIONS IN ART 500
 IN THE NEC".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 PLEASE SEE FIRE REVIEW COMMENTS THAT
 WILL AFFECT ELECTRICAL PLANS.