Plan Review Notes
Plan Review Notes For Permit 02101075
Permit Number 02101075
Review Stop P
Sequence Number 1
Notes
Date Text
2002-12-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBVC-2001 BUILDING
  
 1) SHT A2 PLEASE PROVIDE CALCULATIONS
 FOR MINIMUM FACILITIES PER TABLE 1003.1
 FBC-BLDG AND 403.1 FBC-PLMG.
 2) SHT A2 IF TOILET ROOMS ARE PROVIDED,
 THEN EACH PUBLIC AND COMMON USE TOILET
 ROOM SHALL COMPLY WITH 11-4.22. SEC.
 11-4.1.3(11)
 3) SHT A2 MENS REST ROOM, IF TOILET
 STALLS ARE PROVIDED, THEN AT LEAST ONE
 SHALL BE A STANDARD STALL COMPLYING WITH
 11-4.17 PER 11-4.22.4. SEE 11-4.17.3 FOR
 SIZE AND ARRANGEMENT. LAV REQUIRED IN
 STALL.
 4) SHT A2 SHOWER ROOM, SHOWER SHALL COM-
 PLY WITH 11-4.21 AND ALL SUBSECTIONS.
 SHOW DETAIL.
 5) SHT A2 EMPLOYEE'S LOUNGE, SINK SHALL
 COMPLY WITH 11-4.24 AND ALL SUBSECTIONS.
 PLEASE SHOW DETAILS.
 6) SHT A2 DRINKING FOUNTAIN, SHOW DETAIL
 FOR COMPLIANCE WITH SEC. 11-4.15 AND ALL
 SUBSECTIONS. ALSO SEC. 11-4-1-3(10)(A)
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 7) SHT A2 MENS REST ROOM, URNAL SHALL
 COMPLY WITH 11-4.18 AND ALL SUBSECTIONS.
 SHOW DETAIL.
 8) SHT A5 DETAIL #5 PER FBC SEC 1503.4.2
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4 INCHES IN HEIGHT AND SHALL BE PLACED
 IN WALLS OR PARAPETS WITH THE INLET FLOW
 LINE NOT LESS THAN 2 INCHES ABOVE THE
 ROOF SURFACE, EXCLUDING SUMPS, OR MORE
 THAN 4 INCHES ABOVE THE ROOF SURFACE.
 PLANS SHOW 5" TO INLET FLOW LINE.
 9) SHT P-1 P/T LINE FROM WATER HEATER
 SHALL NOT BE TRAPPED. SEC 504.7.1
 10) SHT P-1 WATER ISOMETRIC, WATER HAM-
 MER ARRESTORS REQUIRED IN SEC 604.9
 SHALL BE LOCATED NEAR FIXTURES IN AN
 "EFFECTIVE RANGE" NOT AT TOP OF DROP AS
 SHOWN. PER PDI-WH 201 AND MANUF. INSTALL
 ATION INSTRUCTIONS.
 11) BACKFLOW REQUIRED ON WATER SERVICE.
 12) SHT P-1 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED PER SEC 607.3
 AND 607.3.2 PLEASE ADD TO DETAIL
 13) SHT P-2 PLEASE SHOW LOCATION ON
 SCUPPER DRAINS. SHOW SIZE OF EACH
 SCUPPER DRAIN AND SQUARE FOOTAGE BEING
 DRAINED THRU EACH SCUPPER.
 14) SHT P-3 MATERIALS & EQUIPMENT (L) &
 EXECUTION OF WORK (F) AIR CHAMBERS ARE
 NOT APPROVED. PLEASE DELETE REFERENCES.
  
 REVIEW BY KEN STEVENS