2002-12-03 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| FBVC-2001 BUILDING |
| |
| 1) SHT A2 PLEASE PROVIDE CALCULATIONS |
| FOR MINIMUM FACILITIES PER TABLE 1003.1 |
| FBC-BLDG AND 403.1 FBC-PLMG. |
| 2) SHT A2 IF TOILET ROOMS ARE PROVIDED, |
| THEN EACH PUBLIC AND COMMON USE TOILET |
| ROOM SHALL COMPLY WITH 11-4.22. SEC. |
| 11-4.1.3(11) |
| 3) SHT A2 MENS REST ROOM, IF TOILET |
| STALLS ARE PROVIDED, THEN AT LEAST ONE |
| SHALL BE A STANDARD STALL COMPLYING WITH |
| 11-4.17 PER 11-4.22.4. SEE 11-4.17.3 FOR |
| SIZE AND ARRANGEMENT. LAV REQUIRED IN |
| STALL. |
| 4) SHT A2 SHOWER ROOM, SHOWER SHALL COM- |
| PLY WITH 11-4.21 AND ALL SUBSECTIONS. |
| SHOW DETAIL. |
| 5) SHT A2 EMPLOYEE'S LOUNGE, SINK SHALL |
| COMPLY WITH 11-4.24 AND ALL SUBSECTIONS. |
| PLEASE SHOW DETAILS. |
| 6) SHT A2 DRINKING FOUNTAIN, SHOW DETAIL |
| FOR COMPLIANCE WITH SEC. 11-4.15 AND ALL |
| SUBSECTIONS. ALSO SEC. 11-4-1-3(10)(A) |
| FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| STOOPING. |
| 7) SHT A2 MENS REST ROOM, URNAL SHALL |
| COMPLY WITH 11-4.18 AND ALL SUBSECTIONS. |
| SHOW DETAIL. |
| 8) SHT A5 DETAIL #5 PER FBC SEC 1503.4.2 |
| OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| 4 INCHES IN HEIGHT AND SHALL BE PLACED |
| IN WALLS OR PARAPETS WITH THE INLET FLOW |
| LINE NOT LESS THAN 2 INCHES ABOVE THE |
| ROOF SURFACE, EXCLUDING SUMPS, OR MORE |
| THAN 4 INCHES ABOVE THE ROOF SURFACE. |
| PLANS SHOW 5" TO INLET FLOW LINE. |
| 9) SHT P-1 P/T LINE FROM WATER HEATER |
| SHALL NOT BE TRAPPED. SEC 504.7.1 |
| 10) SHT P-1 WATER ISOMETRIC, WATER HAM- |
| MER ARRESTORS REQUIRED IN SEC 604.9 |
| SHALL BE LOCATED NEAR FIXTURES IN AN |
| "EFFECTIVE RANGE" NOT AT TOP OF DROP AS |
| SHOWN. PER PDI-WH 201 AND MANUF. INSTALL |
| ATION INSTRUCTIONS. |
| 11) BACKFLOW REQUIRED ON WATER SERVICE. |
| 12) SHT P-1 WATER HEATER DETAIL, THERMAL |
| EXPANSION CONTROL REQUIRED PER SEC 607.3 |
| AND 607.3.2 PLEASE ADD TO DETAIL |
| 13) SHT P-2 PLEASE SHOW LOCATION ON |
| SCUPPER DRAINS. SHOW SIZE OF EACH |
| SCUPPER DRAIN AND SQUARE FOOTAGE BEING |
| DRAINED THRU EACH SCUPPER. |
| 14) SHT P-3 MATERIALS & EQUIPMENT (L) & |
| EXECUTION OF WORK (F) AIR CHAMBERS ARE |
| NOT APPROVED. PLEASE DELETE REFERENCES. |
| |
| REVIEW BY KEN STEVENS |