Plan Review Notes
Plan Review Notes For Permit 02101075
Permit Number 02101075
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-11-21 00:00:001) PLEASE INDICATE WHAT TYPE OF
 CHEMICALS IF ANY WILL BE STORED IN
 THE BUILDING.
  
 2) PLEASE INDICATE PROPOSED OCCUPANT
 LOADS FOR THE FIRST AND SECOND FLOORS.
 PLEASE BE ADVISED THAT CERTAIN
 RESTRICTIONS APPLY TO SPIRAL STAIRS.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND
 CEILINGS.
  
 4) BUILDING ADDRESS REQUIRED ON
 BUILDING.
  
 5) PLEASE PROVIDE MORE DETAILS ON
 SPIRAL STAIR.
  
 6) ARE THERE ANY FIRE SPRINKLERS
 PLANNED FOR THE BUILDING. IF NONE
 ARE PLANNED, PROPER FIRE SEPARATIONS
 ARE REQUIRED BETWEEN WAREHOUSE AND
 BUSINESS. PLEASE PROVIDE DETAILS.
  
 7) THE SITE PLAN INDICATES A 13' WIDE
 DRIVE WITH 6" CURBS. ALTHOUGH FIRE
 RESCUE CAN USE A 13' WIDE DRIVE, IT
 WOULD BE OPTIMUM TO INCREASE THE
 SIZE OF THE INTERIOR ROAD.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910