Plan Review Notes For Permit 02101075 |
Permit Number |
02101075 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-21 00:00:00 | 1) PLEASE INDICATE WHAT TYPE OF | | CHEMICALS IF ANY WILL BE STORED IN | | THE BUILDING. | | | | 2) PLEASE INDICATE PROPOSED OCCUPANT | | LOADS FOR THE FIRST AND SECOND FLOORS. | | PLEASE BE ADVISED THAT CERTAIN | | RESTRICTIONS APPLY TO SPIRAL STAIRS. | | | | 3) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATIONS FOR WALLS AND | | CEILINGS. | | | | 4) BUILDING ADDRESS REQUIRED ON | | BUILDING. | | | | 5) PLEASE PROVIDE MORE DETAILS ON | | SPIRAL STAIR. | | | | 6) ARE THERE ANY FIRE SPRINKLERS | | PLANNED FOR THE BUILDING. IF NONE | | ARE PLANNED, PROPER FIRE SEPARATIONS | | ARE REQUIRED BETWEEN WAREHOUSE AND | | BUSINESS. PLEASE PROVIDE DETAILS. | | | | 7) THE SITE PLAN INDICATES A 13' WIDE | | DRIVE WITH 6" CURBS. ALTHOUGH FIRE | | RESCUE CAN USE A 13' WIDE DRIVE, IT | | WOULD BE OPTIMUM TO INCREASE THE | | SIZE OF THE INTERIOR ROAD. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|