2002-11-20 00:00:00*************** UNSAT **********
  
 1)NOTE: PLEASE SEE SERVICE ENTRANCE
 CONDUCTORS. NEED TO BE SIZED PER
 240-3C/ 310-16/ 110-14
  
 2)NOTE: PLEASE CLARIFY LOADS AND OCP
 FOR AHU`S. 1&2. MAX OCP? W/ MECH PLANS
 AND UNIT LOADS.
  
 3)NOTE: PLEASE CLARIFY AND PROVIDE
 INFORMATION FOR TYPE OF MATERIALS IN
 GRANULATOR AREA AND MOLDING AREA.
 PLEASE PROVIDE TYPE OF GRANUALS/GRINDING
 PROCESS. PROVIDE CLASS/DIVISION LOCATION
 (IF ANY).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  