Plan Review Notes For Permit 02101075 |
Permit Number |
02101075 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-11-20 00:00:00 | *************** UNSAT ********** | | | | 1)NOTE: PLEASE SEE SERVICE ENTRANCE | | CONDUCTORS. NEED TO BE SIZED PER | | 240-3C/ 310-16/ 110-14 | | | | 2)NOTE: PLEASE CLARIFY LOADS AND OCP | | FOR AHU`S. 1&2. MAX OCP? W/ MECH PLANS | | AND UNIT LOADS. | | | | 3)NOTE: PLEASE CLARIFY AND PROVIDE | | INFORMATION FOR TYPE OF MATERIALS IN | | GRANULATOR AREA AND MOLDING AREA. | | PLEASE PROVIDE TYPE OF GRANUALS/GRINDING | | PROCESS. PROVIDE CLASS/DIVISION LOCATION | | (IF ANY). | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|