Date |
Text |
2003-04-02 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 02100754 |
| ADD: 431 EL VEDADO ST |
| CONT: O/B JERRELL, JAMES |
| TEL: (561)659-1403 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| ACTION: DENIED |
| |
| 1) DISCUSSED PLANS WITH ENGINEER RIZA |
| ALTAN ABOUT CODE ISSUES: |
| A) ANCHOR BOLTS: DIA, LENGTH AND SPAC- |
| ING REQUIREMENTS. SSTD10-99 (UNDER SBC |
| 1999 PRESCRIPTIVE METHOD) FOR EXTERIOR |
| SHEER WALL WAS 19", 4'-0" C/C EXCESIVE. |
| B) TOP/ BOTTOM PLATE TO STUD CONNECTION |
| PLANS INDICATE THE USEAGE OF USP (TPP6) |
| THE CATOLOG (2003 EDITION) INDICATES |
| THIS CONNECTION TOBE A TRUSS MENDING |
| PLATE W/ NO UPLIFT VALUES. |
| |
| 2) FL BLDG CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DOCUMENTS: |
| MISSING (4) INTERNAL PRESSURE COEFFIC- |
| INET: +-.18 |
| |
| 3)1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| |
| 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| |
| 4) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. MISSING REPORTS: |
| A)EXTERIOR SWING DOORS |
| B) WINDOWS |
| C) STORM SHUTTERS |
| D) ROOFING ASSEMBLIES (SHINGLES) |
| |
| 5) PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| FOR ALL NON-IMPACT GLAZING. |
| FBC 1606.1.4. |
| |
| 6) FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. SAMPLE ATTACHED. |
| |
| 7)1606.4.4 ANCHOR METHODS. PROVIDE |
| INFORMATION FOR INSTALLATION OF DOOR |
| AND WINDOW BUCKS. |
| |
| 8)ROOFING UNDERLAYMENT 1507.3.8.1-2 |
| FOR ASPHALT OR FIBERGLASS SHINGLES: |
| THE UNDERLAYMENT SHALL BE A MINIMUM OF |
| TWO LAYERS APPLIED AS FOLLOWS: |
| 1) STARTING AT EAVE, A 19" STRIP OF |
| UNDRELAYMENT SHALL BE APPLIED PARALLEL |
| WITH THE EAVE & FASTENED SUFFICIENTLY |
| TO STAY IN PLACE. |
| 2) STARTING AT THE EAVE,36" WIDE STRIP |
| OF UNDERLAYMENT FELT SHALL BE APPLIED |
| OVER-LAPPING SUCCESSIVE SHEETS 19" AND |
| FASTENED SUFFICIENTLY TO STAY IN PLACE. |
| |
| 10)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)659-8096 X 8412 |
| FAX: (561)659-8026 |