2002-10-29 00:00:00DENIED:MECHANICAL PERMIT 02100699
  
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 2001 FBC(M) TABLE 403.3 OR ASHRAE 62-89.
  
 INDICATE LOCATION SIZE & MATERIAL OF
 OUTSIDE AIR DUCT.
  
 PROVIDE ENERGY CALCS AS PER 2001 FBC
 CHAPTER 13
  
 INDICATE TERMINATION OF CONDENSATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.