2002-10-17 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE MISSING RECEPT FOR
 A/C COND UNIT. 210-63
  
 2)NOTE: PLEASE CLARIFY METER LOCATION,
 NO MORETHAN 8' OF UNPROTECTED CONDUCTORS
 INSIDE BLDG. 230-70 LOCAL AMENDMENTS.
  
 3)NOTE: PLEASE NOTE THAT GROUNDING ELEC-
 -TRODE SYSTEM SHOWS GOING TO CONCRETE
 ENCASED ELECTRODE, PLEASE NOTE IF
 SHOWN THEN ONE WOULD HAVE TO BE INSTALL-
 ED? PLEASE NOTE IF EXISTING BLDG, THEN
 CUTTING/CHIPPING OUT STEEL IS NOT REQ`D
 ONLY WHERE AVAILABLE PER 250-50.
  
 4)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE.
 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372