2002-10-10 00:00:00 | DENIED |
| REFERENCE: FBC-2001 FUEL GAS |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER STANDARD |
| GAS CODE. SEE ATTACHED COPY OF RISER. |
| 2. TYPE OF GAS, (LP OR NATURAL) |
| 3. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 GAS CODE SECS. 401.8 THRU |
| 402.5.2 & TABLES 402(1) THRU 402(34). |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES(A)(3). |
| 5. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER THE FBC-2001 GAS |
| CODE SEC 304. |
| 6. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| 7. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| 8) SHOW LOCATION OF EACH PRESSURE REGU- |
| LATOR. SHUT OFF VALVE AND UNION REQUIRED |
| UPSTREAM OF REGULATOR. |
| |