2002-10-10 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE. SEE ATTACHED COPY OF RISER.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 GAS CODE SECS. 401.8 THRU
 402.5.2 & TABLES 402(1) THRU 402(34).
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES(A)(3).
 5. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER THE FBC-2001 GAS
 CODE SEC 304.
 6. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 7. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 8) SHOW LOCATION OF EACH PRESSURE REGU-
 LATOR. SHUT OFF VALVE AND UNION REQUIRED
 UPSTREAM OF REGULATOR.
  
 REVIEW BY KEN STEVENS
 ANY QUESTIONS PLEASE CALL
 (561) 659-8096 EXT 8377