Plan Review Notes For Permit 02100324 |
Permit Number |
02100324 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-07-14 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 02100324 | | ADD: 5400 EAST AV | | CONT: CATALFUMO | | TEL: (561)307-4836 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | REVISION# 2 | | ACTION: DENIED | | | | 1) AWNING: W.P.B. ADMINISTRATIVE CODE | | 104.1.1 SEPERATE PERMIT IS REQUIRED FOR | | AWNINGS. | | | | 2) AWNING: 2003.7 TO BE DESIGNED BY A | | FL REGISTERED PROFESSIONAL ENGINEER. | | | | 3) NEW DOOR AND WINDOW OPENINGS, MISSING | | PRODUCT INFORMATION: | | FL BLD CODE 1606.1.5: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORT, SBCCI OR DADE COUNTY | | REPORT ARE ACCEPTED. | | | | 4) NO INFORMATION ON THE NEW OPENINGS, | | PLANS DO NOT INDICATE FILLED CELL AT | | OPENINGS? 104.2.2.WHAT IS THE DROPPED | | HEADER OVER THE NEW OPENINGS MADE OF? | | HOW IS IT SUPPORTED? | | | | 5) 1707.4.4.2 TAPERED BUCKS: | | SHALL EXTEND BEYOND THE INTERIOR FACE | | OF THE WINDOW OR DOOR FRAME SUCH THAT | | FULL SUPPORT OF THE FRAME IS SUPPORTED. | | | | 6)THE VALUE OF THE PROJECT HAS INCREASED | | HOW MUCH? PERMIT VALUES SHOULD ALSO | | REFLECT THE INCREASE IN THE PROJECT. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|