2003-07-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02100324
 ADD: 5400 EAST AV
 CONT: CATALFUMO
 TEL: (561)307-4836
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 REVISION# 2
 ACTION: DENIED
  
 1) AWNING: W.P.B. ADMINISTRATIVE CODE
 104.1.1 SEPERATE PERMIT IS REQUIRED FOR
 AWNINGS.
  
 2) AWNING: 2003.7 TO BE DESIGNED BY A
 FL REGISTERED PROFESSIONAL ENGINEER.
  
 3) NEW DOOR AND WINDOW OPENINGS, MISSING
 PRODUCT INFORMATION:
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
  
 4) NO INFORMATION ON THE NEW OPENINGS,
 PLANS DO NOT INDICATE FILLED CELL AT
 OPENINGS? 104.2.2.WHAT IS THE DROPPED
 HEADER OVER THE NEW OPENINGS MADE OF?
 HOW IS IT SUPPORTED?
  
 5) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 6)THE VALUE OF THE PROJECT HAS INCREASED
 HOW MUCH? PERMIT VALUES SHOULD ALSO
 REFLECT THE INCREASE IN THE PROJECT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026