2002-10-28 00:00:00 | DENIED |
| REFERENCE: FBC-2001 CHAPTER 11 |
| FBC-2001 PLUMBING |
| |
| 1) SHT A-1 NEW RESTROOM,(W-108A), ADJAC- |
| ENT TO COFFEE ROOM SHALL COMPLY WITH SEC |
| 11-4.22 PER 11-4.1.3(11). MINIMUM WIDTH |
| REQUIRED IS 5'3", AND 5'0" IS SHOWN. |
| 2) SHT A-1 WOMENS, (W-114), HDCP STALL |
| MINIMUM WIDTH IS 5'3" AND 5'0" IS SHOWN. |
| 3) SHT A-1 DOORS SHALL NOT OPEN INTO THE |
| CLEAR FLOOR SPACE OR UNOBSTRUCTED 5' |
| TURNING RADIUS IN ROOMS W-125 & W-126. |
| 4) SHT A-2 PLUMBING NOTES, AIR CHAMBERS |
| ARE NOT APPROVED. PLEASE DELETE REFEREN- |
| CE. WATER HAMMER ARRESTORS ONLY REQUIRED |
| BY SEC. 604.9 SHALL BE INSTALLED. |
| 5) SHT A-2 SANITARY RISER DIAGRAM, FLOOR |
| DRAINS IN MEN'S AND WOMEN'S SHOWER AREA |
| ARE NOT VENTED. FLOOR DRAIN SHOWN IN |
| MEN'S REST ROOM W-126 IS NOT SHOWN ON |
| THE RISER DIAGRAM. |
| 6) WATER RISER DIAGRAM IS REQUIRED. IF |
| WATER HAMMER ARRESTORS ARE SHOWN, THEY |
| SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| "EFFECTIVE RANGE" NOT OVERHEAD IN CEIL- |
| ING. |
| 7) SHT A-4 COFFEE ROOM SINK SHALL COMPLY |
| WITH 11-4.24 AND ALL SUBSECTIONS. PLEASE |
| SHOW ON DETAIL. |
| 8) TABLE 403.1 REQUIRES DRINKING FOUNT- |
| AINS AND A SERVICE SINK. PLEASE INDICATE |
| IF THESE FIXTURES ARE PROVIDED. |
| |