2002-10-29 00:00:00PROVISO:
  
 FIRE DAMPERS SHALL COMPLY WITH THE
 REQUIREMENTS OF UL 555.PROVIDE
 MANUFACUTURER SUBMITTAL AND
 INSTALLATION INSTRUCTIONS ON THE
 JOBSITE AT THE TIME OF INSPECTION.
 2001 FBC(M) 607.1.1 & 607.6.
  
 NO COMBUSTIBLES ABOVE THE CEILING IN THE
 RETURN AIR PLENUM.2001 FBC(M)
 602.1.1.
  
 PLANS DO NOT INDICATE DUCT SMOKE
 DETECTORS.AS PER 2001 FBC(M) 606.2.1,
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY AIR SYSTEMS WITH A DESIGN
 CAPACITY GREATER THAN 2,000 CFM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.