2002-10-29 00:00:00 | PROVISO: | | | | FIRE DAMPERS SHALL COMPLY WITH THE | | REQUIREMENTS OF UL 555.PROVIDE | | MANUFACUTURER SUBMITTAL AND | | INSTALLATION INSTRUCTIONS ON THE | | JOBSITE AT THE TIME OF INSPECTION. | | 2001 FBC(M) 607.1.1 & 607.6. | | | | NO COMBUSTIBLES ABOVE THE CEILING IN THE | | RETURN AIR PLENUM.2001 FBC(M) | | 602.1.1. | | | | PLANS DO NOT INDICATE DUCT SMOKE | | DETECTORS.AS PER 2001 FBC(M) 606.2.1, | | SMOKE DETECTORS SHALL BE INSTALLED IN | | SUPPLY AIR SYSTEMS WITH A DESIGN | | CAPACITY GREATER THAN 2,000 CFM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|