2002-11-14 00:00:00 | BUILDING DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) STRUCTURE IS LOCATED IN AN "AO" FLOOD |
| ZONE AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |
| 3) NUMBER 11 OF THE PLAN NOTES ON SHEET |
| C1 STATES THAT HURRICANE PANELS ARE |
| REQUIRED IN HVHZ AREAS. THE CITY OF WPB |
| IS NOT LOCATED IN A HIGH VELOCITY |
| HURRICANE ZONE, HOWEVER, IMPACT |
| PROTECTION IS REQUIRED. PLEASE REVISE. |
| |
| 4)THE PLANS DO NOT INDICATE THE LOCATION |
| OF THE ROOF DIAPHRAGM NAILING ZONES 1,2 |
| & 3 THAT ARE LISTED IN THE DIAPHRAGM |
| SCHEDULE ON A6. PLEASE PROVIDE A DIAGRAM |
| SEE CITY OF WPB AMENDMENTS TO FBC |
| REVISED TABLE 2306.1. |
| |
| 5) THE HEAD/JAMB DETAIL ON A4 INDICATES |
| A 2X4 P.T. NAILED WITH 1-1/2" CASE |
| HARDENED COIL NAILS. LONGER NAILS OR |
| THINNER BUCK IS NEEDED. PLEASE REVISE. |
| |
| 6) THE FBC SEC.1707.4 REQUIRES WOOD |
| BUCKS THAT ARE 1-1/2" THICK OR GREATER |
| TO EXTEND BEYOND THE INTERIOR FACE OF |
| THE WINDOW OR DOOR FRAME. REVISE HEAD/ |
| JAMB DETAIL (DOOR) ON A4. |
| |
| 7) SPECIFY THE SIZE AND TYPE OF WOOD |
| FOR THE WOOD POST THAT IS SHOWN ON THE |
| PLANS. |
| |
| 8) THE ENGINEERED SITE SPECIFIC PRODUCT |
| APPROVAL SUBMITTAL FORMS REQUIRE THE |
| EMBOSSED SEALED OF THE DESIGNER OF |
| RECORD. |
| |
| 9) THE ENGINEERED DRAWINGS FOR THE |
| MULLIONS DO NOT HAVE THE SITE SPECIFIC |
| PRODUCT APPROVAL SUBMITTAL FORM THAT |
| ACCOMPANIES IT. |
| |
| 10) THE 30" DIAMETER FIXED GLASS WINDOW |
| IN THE FRONT BATH IS NOT INCLUDED ON THE |
| DESIGNER WINDOW SITE SPECIFIC |
| ENGINEERING. PROVIDE PRODUCT APPROVAL |
| FOR THIS WINDOW. |
| |
| 11) PLEASE INSERT REVISED PAGES INTO THE |
| PLANS AND RETURN THE OLD SHEETS TO |
| EXPEDITE PLAN REVIEW. |
| |