Plan Review Notes For Permit 02100199 |
Permit Number |
02100199 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-10-24 00:00:00 | ************ NOTES ****************** | | | | 1)NOTE: PLEASE NOTE MISSING EQUIPMENT | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | PANEL. SIZE PER 250-122 | | | | 2)NOTE: PLEASE NOTE SD`S ARE NOT PERMITT | | -ED IN KITCHENS. MIN 3'. NFPA-72 8-1.4.1 | | .6. | | | | 3)NOTE: PLEASE NOTE DEPENDING ON WALLS | | BEING BUILT IN BEDROOM, NEED RECEPT PER | | 210-52. | | | | 4)NOTE: PLEASE NOTE SIZING OF CONDUIT | | BETWEEN MAIN DISC AND PANEL PER NEC | | TABLE. | | | | PLEASE SEE NOTES REDLINED ON PLANS AND | | REVISE BEFORE ROUGH ELECTRICAL INSPECT- | | -ION. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|