2002-10-24 00:00:00************ NOTES ******************
  
 1)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. SIZE PER 250-122
  
 2)NOTE: PLEASE NOTE SD`S ARE NOT PERMITT
 -ED IN KITCHENS. MIN 3'. NFPA-72 8-1.4.1
 .6.
  
 3)NOTE: PLEASE NOTE DEPENDING ON WALLS
 BEING BUILT IN BEDROOM, NEED RECEPT PER
 210-52.
  
 4)NOTE: PLEASE NOTE SIZING OF CONDUIT
 BETWEEN MAIN DISC AND PANEL PER NEC
 TABLE.
  
 PLEASE SEE NOTES REDLINED ON PLANS AND
 REVISE BEFORE ROUGH ELECTRICAL INSPECT-
 -ION. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW