Plan Review Notes
Plan Review Notes For Permit 02100045
Permit Number 02100045
Review Stop E
Sequence Number 2
Notes
Date Text
2003-06-25 00:00:00*************** UNSAT **************
  
 1)NOTE: RISER NOW SHOWS A MAIN BEING
 INSTALLED OUTSIDE, PLEASE VERIFY OF THE
 200A AND 60A PANELS ARE STILL MCB`S
 (MAIN CIRCUIT BRKR)
 MCB`S ARE NOT REQ`D, HOWEVER IF SHOWN
 ON PLANS, THEN THEY WILL BE REQ`D TO BE
 INSTALLED.
  
 2)NOTE: PLEASE SEE CONDUCTOR SIZE SHOWN
 FOR SUB PANEL. PLEASE HAVE ALL CHANGES
 DONE BY THE ARCH OF RECORD.
 FS 481
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAIN DISC/
 PANEL TO SUB PANEL AND FROM MAIN DISC
 OUTSIDE MAIN,.250-110/250-24
  
 4)NOTE: PLEASE SEE 200 MAIN PANEL,
 SHOWS FEEEDING SUB PANEL W/ 8 CIRCUITS?
 MEANT TO SHOW 2?
  
 5)NOTE: PLEASE SEE 3.2 KW SHOWN FOR EACH
 15A CIRCUIT. PLEASE SEE THAT THESE ARE
 OVERLOADED.
  
 6)NOTE: PLEASE SEE MISSING KITCHEN
 COUNTERSPACE RECEPT PER 210-52C-1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]