Plan Review Notes For Permit 02100045 |
Permit Number |
02100045 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-06-25 00:00:00 | *************** UNSAT ************** | | | | 1)NOTE: RISER NOW SHOWS A MAIN BEING | | INSTALLED OUTSIDE, PLEASE VERIFY OF THE | | 200A AND 60A PANELS ARE STILL MCB`S | | (MAIN CIRCUIT BRKR) | | MCB`S ARE NOT REQ`D, HOWEVER IF SHOWN | | ON PLANS, THEN THEY WILL BE REQ`D TO BE | | INSTALLED. | | | | 2)NOTE: PLEASE SEE CONDUCTOR SIZE SHOWN | | FOR SUB PANEL. PLEASE HAVE ALL CHANGES | | DONE BY THE ARCH OF RECORD. | | FS 481 | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | GROUNDING CONDUCTORS FROM MAIN DISC/ | | PANEL TO SUB PANEL AND FROM MAIN DISC | | OUTSIDE MAIN,.250-110/250-24 | | | | 4)NOTE: PLEASE SEE 200 MAIN PANEL, | | SHOWS FEEEDING SUB PANEL W/ 8 CIRCUITS? | | MEANT TO SHOW 2? | | | | 5)NOTE: PLEASE SEE 3.2 KW SHOWN FOR EACH | | 15A CIRCUIT. PLEASE SEE THAT THESE ARE | | OVERLOADED. | | | | 6)NOTE: PLEASE SEE MISSING KITCHEN | | COUNTERSPACE RECEPT PER 210-52C-1 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|