2002-10-23 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250-66 SHOWN AS #4.
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL "B". SIZE PER 250-122
  
 3)NOTE: PLEASE NOTE A PANEL "C" IS SHOWN
 ON METER/MAIN COMBO AND NOT ON RISER
 OR PLANS? PLEASE SHOW, CONDUIT,WIRE,
 LOCATION ETC 215-5
  
 4)NOTE: PLEASE NOTE THAT PLANS SHOW A
 SD IN KITCHEN. PLEASE NOTE SD IS NOT
 PERMITTED IN KITCHEN PER NFPA-72
 8-1.4.1.6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  