2002-10-31 00:00:00 | |
| BUILDING DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) PROVIDE A COMPLETE SOIL TEST REPORT |
| INDICATING SOIL PREPARATION AND SOIL |
| BEARING CAPACITY. REPORT SHALL HAVE THE |
| WET SIGNATURE, DATE AND EMBOSSED SEAL |
| OF A FL SOIL ENGINEER. |
| |
| 4) PLEASE REVISE THE CONSTRUCTION TYPE |
| LISTED ON A4 TO TYPE VI. |
| |
| 5) SPECIFY THAT THE WWM FOR THE SLAB |
| SHALL BE SUPPORTED BY APPROVED APPROVED |
| MATERIALS OR SUPPORTS AT SPACINGS NOT TO |
| EXCEED 3 FEET. SEE 2001 FBC SEC. 1909.3. |
| |
| 6)THE EXPOSURE CATEGORY FOR THE |
| STRUCTURE GIVEN ON A1 IS B NOT C. |
| PLEASE REVISE. |
| |
| 7) SPECIFY ONE HOUR FIRE RATED GLASS |
| BLOCK AT ZERO LOT LINE. REVISE THE GLASS |
| BLOCK DETAIL ON A8 TO SHOW A ONE HOUR |
| RATED GLASS BLOCK ASSEMBLY. |
| |
| 8) PROVIDE A LINTEL SCHEDULE. |
| |
| 9) THE GLASS BLOCK IN THE MASTER BATH |
| ARE IN HAZARDOUS LOCATIONS AND MUST HAVE |
| A MINIMUM UNIFORM FACE THICKNESS OF 0.25 |
| INCH PER FBC 2405.2.2. SPECIFY THIS ON |
| THIS ON THE PLANS. |
| |
| 10) PROVIDE COMPLETE INFORMATION FOR THE |
| 2" STEEL HEADER DETAIL. INDICATE THE |
| WELD TYPE, THICKNESS OF STEEL, ETC. |
| |
| 11) PLEASE CORRECT THE CONSTRUCTION TYPE |
| LISTED ON A4 TO TYPE VI. |
| |
| 12) PROVIDE CALCULATIONS WHICH INDICATE |
| THAT THE REQUIRED NET FREE VENTILATING |
| AREA WILL BE PROVIDED BY THE AREAS THAT |
| DO NOT HAVE THE STYROFOAM TRIM. |
| |
| 13) SPECIFY THE SIZE OF THE WASHERS USED |
| ON THE TAPCONS FASTENING THE GARAGE DOOR |
| BUCKS IN THE DETAIL ON A8. |
| |
| 14) REVISE THE SWING DOOR BUCK DETAIL ON |
| A8 TO COMPLY WITH FBC 1707.4.4.2. |
| |
| 15) PROVIDE A STRUCTURAL DETAIL OF THE |
| BOLLARD/3" STEEL POST IN THE GARAGE. |
| |
| 16) SPECIFY ON THE PLANS THAT THE DOOR |
| BETWEEN THE GARAGE AND CONDITIONED SPACE |
| IS SOLID CORE OR INSULATED AS REQUIRED |
| BY CHAPTER 13 OF THE FBC. |
| |
| 17) PROVIDE (2) COPIES OF A KEY PLAN AND |
| INSTALLATION SCHEDULE INDICATING THE |
| SPECIFIC TYPE OF FASTENERS THAT ARE TO |
| BE USED FOR THE STORM PANELS. INDICATE |
| THE MOUNTING OPTIONS THAT WILL BE USED. |
| THIS INFORMATION IS REQUIRED PRIOR TO |
| PERMIT OR A SEPARATE PERMIT WILL BE |
| REQUIRED WITH ADDITIONAL FEES. |
| |
| 18) THE PRODUCT APPROVALS FOR THE |
| SLIDING GLASS DOORS IS MISSING PAGE 2 |
| AND THE DRAWINGS HAVE THE WRONG |
| ACCEPTANCE NUMBER. |
| |
| 19) PROVIDE MANUFACTURES SPECS. AND UL |
| LISTING INFORMATION FOR ONE HOUR RATED |
| GLASS BLOCK ASSEMBLIES. |
| |
| 20) PRODUCT APPROVALS WERE SUBMITTED FOR |
| GLASS BLOCK FROM TWO DIFFERENT MANUFACT- |
| URERS. SUBMIT THE ONE THAT IS TO BE |
| INSTALLED ALONG WITH THE INFORMATION |
| REQUESTED ABOVE AN THAT CORRESPONDS TO |
| THE DETAIL ON THE PLANS. |
| |
| 21) IN ORDER TO MEET THE WINDLOAD |
| PRESSURES LISTED ON THE PLANS, THE FIXED |
| GLASS WINDOWS WILL HAVE TO BE TEMPERED |
| GLASS ACCORDING TO THE PRODUCT APPROVALS |
| THAT WERE SUBMITTED. SPECIFY ON THE |
| PLANS THAT THESE WINDOWS WILL HAVE |
| TEMPERED GLASS. |
| |
| 22) THE SITE SPECIFIC PRODUCT APPROVALS |
| FOR THE SIDE SWINGING DOORS ARE REQUIRED |
| TO BE SIGNED, SEALED AND DATED BY THE |
| DESIGNER OF RECORD OF THE STRUCTURE. THE |
| LOCATION OF THE STRUCTURE IS REQUIRED TO |
| BE ON THE FORM. PROVIDE THE TEST REPORTS |
| FOR MISSLE IMPACT AS REQUIRED BY GENERAL |
| NOTE 7.5 ON THE FORM. |
| |
| 23) THE DESIGN PRESSURES LISTED ON THE |
| PLANS FOR SOME OF THE SINGLE HUNG |
| WINDOWS EXCEED THE DESIGN PRESSURES IN |
| THE PRODUCT APPROVALS. SOME WILL REQUIRE |
| TEMPERED GLASS TO COMPLY. |
| |
| 24) PROVIDE PRODUCT APPROVALS FOR |
| STRUCTURAL MULLIONS AT WINDOWS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |