Date |
Text |
2002-11-06 00:00:00 | BUILDING DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3)FL BLDG 1909.3 (EXEPTION# 2) |
| CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| PORTED BY APPROVED MATERIALS OR SUPPORTS |
| AT SPACING NOT TO EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURER'S SPEC. |
| |
| 4) SPECICFY THE MAXIMUM SPACING OF THE |
| VERTICAL WALL REINFORCEMENT. |
| |
| 5) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| PROVIDE A SOIL BEARING TEST, SIGNED AND |
| SEALED BY A FL SOIL ENGINEER. |
| |
| 6) THE TYPICAL WALL SECTION ON SHEET 1 |
| INDICATES R-19 INSULATION AND THE ENERGY |
| CALCULATIONS LIST R-30. PLEASE CORRECT. |
| |
| 7) SPECIFY ON THE PLANS THAT THE BOTTOM |
| OF THE FOOTER SHALL BE A MINIMUM OF 12 |
| INCHES BELOW FINISH GRADE AND THE LOWEST |
| BUILDING FLOOR ELEVATION AT PERIMETER OF |
| MONOLITHIC FOUNDATION AT HABITABLE AREAS |
| SHALL BE A MINIMUM OF 4 INCHES ABOVE |
| FINISH GRADE. FBC 1804.1.3 AND CITY OF |
| W.P.B. AMENDMENTS 1804.1.7. |
| |
| 8) INDICATE THE INTERNAL PRESSURE |
| COEFFICENT ON THE PLANS.SEE FBC 1606.1.7 |
| |
| 9) THE FRONT (EGRESS) DOOR IS REQUIRED |
| TO PROVIDE A CLEAR OPENING OF NOT LESS |
| THAN 32 INCHES WIDE. SEE FBC 1012.1. |
| |
| 10) PROVIDE ATTIC ACCESS OPENING. SEE |
| FBC 2309.7. |
| |
| 11) SPECIFY THE CEILING FINISH MATERIAL |
| FOR THE COVERED PORCH AND FRONT ENTRY. |
| |
| 12) THE OWNER/AGENT IS REQUIRED TO SIGN |
| THE ENERGY CALC. FORM. FBC CHAPTER 13 |
| |
| 13)PROVIDE (2) COPIES OF AN INSTALLATION |
| SCHEDULE AND CORRESPONDING KEY PLAN FOR |
| THE STORM PANELS. |
| |
| 14) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - STRUCTURAL WINDOW MULLIONS |
| - SINGLE HUNG WINDOWS (THE ONE SUBMITTED |
| IS MISSING SEVERAL PAGES OF DRAWINGS AND |
| OTHERS ARE ILLEGIBLE) |
| - SINGLE OUTSWING STEEL DOOR (MISSING |
| SHEET 3 OF THE DRAWINGS) |
| - ROOFING MATERIALS (ONES SUBMITTED ARE |
| NOT ACCEPTABLE) |
| - DOUBLE OUTSWING DOORS |
| - HORIZONTAL SLIDING WINDOWS |
| - SLIDING GLASS DOORS |
| - GLASS BLOCK |
| - ARCHED FIXED GLASS WINDOWS |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |