Plan Review Notes
Plan Review Notes For Permit 02100015
Permit Number 02100015
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-24 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO PLANS,AND RESUBMIT FOR REVIEW:
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE RISER DIAGRAM DOES NOT SHOW THE
 MAIN DISCONNECT REQUIRED BY 230-70 NEC
 & 230-70(A) CWPB AMMENDMENTS.
  
 A) ALSO NOTE THAT IF THE MAIN IS TO BE
 LOCATED IN THE PANEL,THE #6 EQ. GND.
 MUST BE REMOVED PER 250-24(A)(1).
  
 3} THE NOTE REGARDING LOAD CALCS SHOULD
 REFER TO 220-30 INSTEAD OF 230-30.
  
 4} PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM PER 250-50(A),(B) &
 (C),REFERENCE FOOTER STEEL.
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 6} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 7} PLEASE NOTE KITCHEN COUNTERTOP
 RECEPTACLES MUST COMPLY WITH
 210-8(A)(6)GFI'S.
  
 8} NOTE GARAGE RECEPTACLES AS GFI PER
 210-8(A)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R.(BILL) TROBAUGH
 ELECTRICAL PLANS REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392