2002-10-24 00:00:00 | UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| PLEASE PROVIDE THE FOLLOWING |
| INFORMATION,MAKE ANY NECESSARY CHANGES |
| TO PLANS,AND RESUBMIT FOR REVIEW: |
| |
| 1} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 2} THE RISER DIAGRAM DOES NOT SHOW THE |
| MAIN DISCONNECT REQUIRED BY 230-70 NEC |
| & 230-70(A) CWPB AMMENDMENTS. |
| |
| A) ALSO NOTE THAT IF THE MAIN IS TO BE |
| LOCATED IN THE PANEL,THE #6 EQ. GND. |
| MUST BE REMOVED PER 250-24(A)(1). |
| |
| 3} THE NOTE REGARDING LOAD CALCS SHOULD |
| REFER TO 220-30 INSTEAD OF 230-30. |
| |
| 4} PLEASE SHOW GROUNDING ELECTRODE |
| SYSTEM PER 250-50(A),(B) & |
| (C),REFERENCE FOOTER STEEL. |
| |
| 5} PLEASE LIST THE REQ'D BATH(S) |
| CIRCUIT(S). PER 210-11-C-3 |
| MUST BE 20A AND #12AWG. |
| |
| 6} PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CIRCUITS ON PANEL |
| SCHEDULE PER 210-12. |
| |
| 7} PLEASE NOTE KITCHEN COUNTERTOP |
| RECEPTACLES MUST COMPLY WITH |
| 210-8(A)(6)GFI'S. |
| |
| 8} NOTE GARAGE RECEPTACLES AS GFI PER |
| 210-8(A)(2). |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |