Plan Review Notes
Plan Review Notes For Permit 02091746
Permit Number 02091746
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-10-01 00:00:001) PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE WILL ADVISE WHEN THE
 FIRE ALARM SYSTEM IS ACTIVATED.
  
 2) WHY ARE THERE NO SPEAKER STROBES
 INSTALLED IN THE RECORDING STUDIO OR
 LARGE MUSIC ROOM LOCATED ON THE SECOND
 FLOOR.
  
 3) PLEASE NOTE ON THE PLANS THAT SMOKE
 DETECTORS ARE TO BE INSTALLED NO
 CLOSER THAN 3 FEET FROM AIR CONDITIONER
 DIFFUSERS. ALSO THE PLACEMENT OF
 SMOKE DETECTORS ARE NOT TO EXCEED
 MANUFACTURER'S REQUIREMENTS.
  
 4) IT WAS NOTED THAT SMOKE DETECTORS
 ARE INSTALLED IN TWO OF THE STAIRS ON
 THE THIRD LEVEL EXCEPT FOR ONE. WHAT
 IS THE DIFFERENCE.
  
 5) ALL INITIATING DEVICES ARE TO
 ACTIVATE THE FIRE ALARM SYSTEM.
  
 6) THE LOCATION OF THE FIRE ALARM
 CONTROL PANEL IS NOT VERY GOOD. IT
 HAS VERY LIMITED QUICK ACCESS AND TRAVEL
 IS REQUIRED DOWN A HALLWAY. IT APPEARS
 THAT NO REMOTE ANNUNICIATORS HAVE BEEN
 PROVIDED. ONE WAS LOCATED BUT HOW IS
 ACCESS PROVIDED.
 7) ARE THERE ANY SECURITY DEVICES LIKE
 MAG LOCKS OR OTHER DEVICES CONNECTED
 TO THE FIRE ALARM PANEL. PLEASE ADVISE.
  
 8) KITCHEN HOOD SYSTEM SHALL BE
 CONNECTED TO THE FIRE ALARM SYSTEM.
  
 9) SPEAKER STROBE LOCATED IN VALET
 RAMP. PLEASE ADVISE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910