Plan Review Notes For Permit 02091707 |
Permit Number |
02091707 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-10-22 00:00:00 | ********** NOTES REDLINED ********* | | | | 1)NOTE: PLEASE NOTE SD NOT PERMITTED IN | | KITCHEN, MUST BE A MIN OF 3'. NFPA-72 | | 8-1.4.1.6 | | | | 2)NOTE: PLEASE NOTE SD IN HALLWAY TO | | MOVE OR TO ADD SECOND DETECTOR. | | 8-1.4 | | | | 3)NOTE: MISSING EQUIPMENT GROUNDING | | CONDUCTOR BETWEEN MAIN AND PANEL. | | SIZE PER 250-122 | | | | 4)NOTE: PLEASE NOTE SIZING OF CONDUIT | | BETWEEN MAIN DISC AND PANEL. PER NEC | | TABLES. MIN 2". | | | | PLEASE REVISE PLANS BEFORE ROUGH. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|