2002-10-21 00:00:00******* NOTES REDLINED ON PLANS ****
  
 SD NOT PERMITTED IN KITCHEN PER
 NFPA-72 8-1.4.1.6
  
 NO EQUIPMENT GRNDING CONDUCTOR BETWEEN
 MAIN AND PANEL. 250-122
  
 PLEASE NOTE SIZING OF CONDUIT BETWEEN
 MAIN AND PANEL PER TABLE 9 NEC. MIN 2"
 CONDUIT.
  
 PLEASE REVISE AND SUBMIT BEFORE ROUGH.
  