Plan Review Notes For Permit 02091706 |
Permit Number |
02091706 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-10-21 00:00:00 | ******* NOTES REDLINED ON PLANS **** | | | | SD NOT PERMITTED IN KITCHEN PER | | NFPA-72 8-1.4.1.6 | | | | NO EQUIPMENT GRNDING CONDUCTOR BETWEEN | | MAIN AND PANEL. 250-122 | | | | PLEASE NOTE SIZING OF CONDUIT BETWEEN | | MAIN AND PANEL PER TABLE 9 NEC. MIN 2" | | CONDUIT. | | | | PLEASE REVISE AND SUBMIT BEFORE ROUGH. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|