Notes
Date Text
2002-09-30 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} THE CONDUCTOR SIZE REQUIRED BY NEC
 310-15(B)(6) FOR 400 AMPS FOR 400 MCM.
  
 A) 3-400 MCM IN A 2" PVC IS NOT
 ALLOWED. SEE APPROPRIATE TABLE FOR THE
 CONDUIT TYPE BEING USED.
  
 B) TABLE 210-66 LISTS 1/0 AS THE
 GEC SIZE FOR 400 MCM.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 THIS CAN BE BROUGHT IN AS A SUBMITTAL
 OR FAXED TO ME,FILL OUT THE FORM IN
 EITHER CASE (ATTACHED),AND KEEP A COPY
 OF THE RATING AND ON THE
 JOB FOR THE INSPECTOR.GET THIS
 INFORMATION FROM FPL BEFORE INSPECTION.
  