Date |
Text |
2002-10-29 00:00:00 | BUILDING DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) STRUCTURE IS LOCATEDIN AN "AO" FLOOD |
| ZONE AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |
| 3) ON SHEET A5 THERE IS A DETAIL TAG FOR |
| 1 ON A8. HOWEVER THERE IS NO SHEET A8. |
| PLEASE CORRECT. |
| |
| 4)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| PLEASE INCLUDE ALL OF THIS REQUIRED |
| INFORMATION ON THE PLANS. |
| |
| 5) NUMBER 11 OF THE PLAN NOTES ON SHEET |
| C1 STATES THAT HURRICANE PANELS ARE |
| REQUIRED IN HVHZ AREA. THE CITY OF WPB |
| IS NOT LOCATED IN A HIGH VELOCITY |
| HURRICANE ZONE, HOWEVER, IMPACT |
| PROTECTION IS REQUIRED. PLEASE REVISE. |
| |
| 6)THE PLANS DO NOT INDICATE THE LOCATION |
| OF THE ROOF DIAPHRAGM NAILING ZONES 1,2 |
| & 3 THAT ARE LISTED IN THE DIAPHRAGM |
| SCHEDULE AND BRACING LEGEND ON A6. |
| |
| 7) THERE IS NO TRUSS CONNECTOR SCHEDULE |
| GIVEN TO CORRESPOND WITH THE CONNECTOR |
| DESIGNATIONS ON A6. |
| |
| 8)THE KEY PLAN AND INSTALLATION SCHEDULE |
| FOR THE STORM PANELS LIST INCORRECT |
| OPENING SIZES FOR #S 2,3 & 13. PLEASE |
| CORRECT. |
| |
| 9) THE GLASS BLOCK AT THE MASTER BATH |
| TUB IS REQUIRED TO HAVE A MINIMUM |
| UNIFORM FACE THICKNESS OF 0.25 INCH PER |
| FBC 2405.2.1 AND 2405.2.2(5). |
| |
| 10) THE FBC SEC.1707.4.4.2 REQUIRES |
| WINDOW AND DOOR ASSEMBLIES WITH BUCKS |
| LESS THAN 1-1/2" THICK TO BE ANCHORED |
| THROUGH THE BUCK TO THE ROUGH OPENING |
| SUBSTRATE. |
| |
| 11) THE SITE SPECIFIC PRODUCT APPROVAL |
| FORMS REQUIRE THE EMBOSSED SEAL OF THE |
| DESIGNER OF RECORD IN ADDITION TO HIS |
| SIGNATURE. |
| |
| 12) THERE WAS NO SITE SPECIFIC PRODUCT |
| APPROVAL FORM SUBMITTED WITH THE |
| UNCLIPPED VERTICAL MULLION DRAWINGS. |
| |
| 13) THE DIMENSIONS GIVEN IN THE DRAWINGS |
| FOR THE DESIGNER WINDOWS DO NOT |
| CORRESPOND WITH SEVERAL OF THE FIXED |
| GLASS WINDOWS SHOWN ON THE PLANS. PLEASE |
| REVIEW AND REVISE FOR THE SIZES ON THE |
| PLANS. CHECK TO BE SURE THAT THE WIND- |
| LOAD PRESSURES ARE ADEQUATE. |
| |
| 14) PROVIDE PRODUCT APPROVAL FOR |
| HORIZONTAL STRUCTURAL MULLIONS. |
| |
| 15) PLEASE INSERT REVISED PAGES INTO THE |
| PLANS. RETURN OLD PLANS TO EXPEDIATE |
| PLAN REVIEW. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |