Plan Review Notes
Plan Review Notes For Permit 02091413
Permit Number 02091413
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-01 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND MAKE ANY NECESSARY
 CHANGES ON THE PLANS.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE RISER DIAGRAM SHOWS AN EXISTING
 METER BUT THE NOTE AT THE METER
 LOCATION INDICATE A NEW METER BEING
 RELOCATED,PLEASE CLARIFY.
  
 3} THE NOTE ON THE GROUNDING ELECTRODE
 SYSTEM IS UNACCEPTABLE FOR
 REVIEW.PLEASE PROVIDE DETAILS.
  
 4} THE NOTE ABOUT THE SERVICE CONDUIT
 BEING ROUTED IN THE CRAWL SPACE IS IN
 VIOLATION OF ARTICLE 230-6 NEC AND
 230-70(A) WEST PALM BEACH AMMENDMENTS.
 IN EITHER CASE A MAIN DISCONNECT WOULD
 BE REQUIRED PER 225-31 & 225-32 NEC.
  