Plan Review Notes For Permit 02091320 |
Permit Number |
02091320 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-10-01 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE NOTE THAT THERE IS NO ELECTRICAL | | CONTRACTOR SIGNED ON THIS APPLICATION. | | A SEPARATE ELECTRICAL PERMIT IS REQUIRED | | | | THE ELECTRICAL SCHEMATIC EXCLUDED THE | | TIME CLOCK REQUIRED BY THE FLORIDA | | BUILDING CODE ENERGY EFFICIENCY | | CHAPTER,SECTION 612.1ABC.2.3.3 | | | | PLEASE PROVIDE A LOAD CALCULATION FOR | | THE SERVICE SUPPLYING EXISTING AND ALL | | ADDITIONAL LOADS FOR THE SCOPE OF THIS | | APPLICATION. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT.8392 |
|