Plan Review Notes
Plan Review Notes For Permit 02091320
Permit Number 02091320
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-01 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THAT THERE IS NO ELECTRICAL
 CONTRACTOR SIGNED ON THIS APPLICATION.
 A SEPARATE ELECTRICAL PERMIT IS REQUIRED
  
 THE ELECTRICAL SCHEMATIC EXCLUDED THE
 TIME CLOCK REQUIRED BY THE FLORIDA
 BUILDING CODE ENERGY EFFICIENCY
 CHAPTER,SECTION 612.1ABC.2.3.3
  
 PLEASE PROVIDE A LOAD CALCULATION FOR
 THE SERVICE SUPPLYING EXISTING AND ALL
 ADDITIONAL LOADS FOR THE SCOPE OF THIS
 APPLICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392