Plan Review Notes
Plan Review Notes For Permit 02091306
Permit Number 02091306
Review Stop P
Sequence Number 1
Notes
Date Text
2002-10-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-2.1 HANDICAP STALL MEN'S REST
 ROOM, WATER CLOSET CAN NOT INTRUDE INTO
 THE CLEAR FLOOR SPACE FOR HDCP LAV.
 2) SHT A10.1 DETAIL #2, FLUSH CONTROLS
 TO BE ON CLEAR SIDE OF W/C SEC 11-4.16.5
 3) SHT A10.1 DETAIL #4, TOILET ROOM TO
 BE ADAPTABLE. 11-4.1.3(11). PLEASE SHOW
 DETAILS. W/C TO BE 18" OFF WALL, SHOW
 BACKING FOR GRAB BARS, LAV TO BE ABLE TO
 BE SET AT 34" ECT.
 4) SHT A10.1 DETAIL #3, 1 URNAL TO BE
 HDCP PER 11-4.22.5. SHOW HEIGHT SECTION
 11-4.18.2, AND CLEAR FLOOR SPACE SECTION
 11-4.18.3.
 5) SHT P.1 SINK IN SACRISTY SHALL DRAIN
 TO SANITARY. SECTION 301.3
 6) SHTS P.2/P.3 RELIEF VALVE DRAIN SHALL
 NOT BE TRAPPED. SECTION 504.7.1
 7) SHT P.3 WATER RISER DIAGRAM, WATER
 HEATER SHALL REQUIRE THERMAL EXPANSION
 CONTROL. SECTION 607.3.2
 SHT P-3 WATER RISER DIAGRAM, WATER HAMM-
 ER ARRESTORS REQUIRED BY SECTION 604.9
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE", NOT AT THE TOP OF THE
 DROP IN CEILING AS SHOWN PER PDI-WH 201
 AND MANUFACTURE INSTALLATION INSTRUCTION
 8) SEPARATE IRRIGATION PERMIT AND PLANS
 ARE REQUIRED. PLUMBING CONTRACTOR SHALL
 PROVIDE A VALVE AND ADAPTOR FOR IRRG.
 CONTRACTOR.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377