Plan Review Notes For Permit 02091306 |
Permit Number |
02091306 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-10-10 00:00:00 | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | REQUIRES NOTIFICATION TO ALARM STROBE | | IN NORMALLY OCCUPIED AREAS OR A SUPER- | | VISORY SIGNAL TO BE INDICATED AT A | | CONSTANTLY ATTENDED LOCATION OR CAUSES | | AN ALARM SIGNAL. NFPA 90A 4-4.4.3 & | | 4-4.4.2. | | | | 2001 FBC(M) 306.5, WHERE EQUIPMENT AND | | APPLIANCES REQUIRING ACCESS ARE | | INSTALLED ON ROOFS OR ELEVATED | | STRUCTURES AT A HEIGHT EXCEEDING 16 FT, | | SUCH ACCESS SHALL BE PROVIDED BY A | | PERMANENT APPROVED MEANS OF ACCESS. | | SUCH ACCESS SHALL NOT REQUIRE CLIMBING | | OVER OBSTRUCTIONS GREATER THAN 30 | | INCHES.PLAN SHEET A-3.0 - ROOFPLAN | | KEYNOTES #8 MAINTENANCE ACCESS HATCH, | | NO #8 IDENTIFIED ON PLAN. | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|