2002-10-07 00:00:00 | **************** UNSAT ************ | | | | 1)NOTE: PLEASE NOTE TITLE BLOCK MUST | | CONTAIN LICENSE # FOR ENGINEER OF | | RECORD. PER FAC. 61G15-23.002 | | | | 2)NOTE: PLEASE CLARIFY LOCATION OF REQ`D | | GFI FOR A/C UNIT OUTSIDE PER 210-63 | | | | 3)NOTE: PLEASE NOTE CLEARENCE PER 110-26 | | FOR PANEL "B". SHOWN W/ COUNTERTOP | | INFRONT OF PANEL. | | | | 4)NOTE: PLEASE NOTE IF THERE ARE GOING | | TO BE ANY LOW VOLTAGE/ SOUND SYSTEM | | INSTALLED. PLANS WILL BE REQ`D NOW OR | | SUBMITTED AT TIME OF APPLICATION FOR | | PERMIT. | | | | 5)NOTE: PLEASE NOTE RISER DIAGRAM SHOWS | | AN EQUIPMENT GROUNDING CONDUCTOR BETWEEN | | GUTTER AND MAIN DISC`S. PLEASE NOTE, | | NO EQUIPMENT GRND IS INSTALLED DUE TO | | PARALELLING THE NEUTRAL. PER 250-24 | | | | 6)NOTE: PLEASE SUBMIT THE AIC RATING FOR | | MAIN DISC`S. MAINS/PANELS/BRKRS/ ALL | | MUST BE RATED FOR THE AVAILABLE FAULT | | CURRENT. PER 110-9. | | | | 7)NOTE: PLEASE SHOW LOCATION OF SERVICE | | ON BLDG. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|