2002-10-24 00:00:00 | |
| BUILDING PLAN REVIEW |
| PERMIT: 02091306 |
| ADD: 3600 AUSTRALIAN AVE |
| CONT: HEDRICK BROTHERS |
| TEL: (561)242-4303 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)FL S. S. 553.71(7) " THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| CY CLASSIFICATION AS DEINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS |
| 5,000 SQ FT IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| 105.13.1 THE ENFORCING AGENCY SHALL |
| REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| SRUCTURAL INSPECTIONS ON A THRESHOLD |
| BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| TION PLAN PREPARED BY THE ENGINEER OF |
| RECORD. THE STRUCTURAL INSPECTION PLAN |
| MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| CY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| IC INSPECTION PROCEDURES AND SCHEDULES |
| SO THAT THE BUILDING CAN BE ADEQUATELY |
| INSPECTED FOR COMPLIANCE WITH THE |
| PERMITTED DOCUMENTS. |
| |
| 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| SUBMIT SOILS REPORT WITH THE MINIMUM |
| SAFE BEARING CAPACITY. |
| |
| 3) THE PLANS DO NOT INDICATE THE USE OF |
| FIRE SPRINKLERS, FBC 903.7.2.4 REQUIRES |
| ASSEMBLY OCC WITH AN OCCUPANCY LOAD |
| GREATER THAN 300 PERSONS TO HAVE FIRE |
| SPRINKLER PROTECTION. SEE EXCEPTIONS! |
| |
| 4) FBC 10.19.10.1.4. ASSEMBLY OCCUPANCY |
| > 200 PERSONS REQUIRE SEATS TO BE FAST- |
| ENED TO THE FLOOR. |
| |
| 5) 1019.7.2. FBC ASSEMBLY OCCUPANCY,EACH |
| DOOR IN A MEANS OF EGRESS FROM AN AREA |
| OF GROUP A OCC. REQUIRES PANIC HARDWARE |
| OR FIRE EXIT HARDWARE. |
| |
| 6) TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY |
| |
| 7)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| WILL THE BLDG BE USED FOR ANYTHING OTHER |
| THAN RELIGIOUS SERVICES? THIS MAY ENACT |
| OTHER CODE SECTIONS? FL ACCESSIBILITY |
| |
| 8)PROVIDE ENERGY CALCULATIONS AND |
| EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| AS REQUIRED BY THE 2001 FLORIDA ENERGY |
| EFFICIENTCY CODE FOR BUILDING CONSTRUC- |
| TION. |
| |
| 9)1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| |
| 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| |
| 10)FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. MISSING REPORTS: |
| A) WINDOWS, FIXED OR CASEMENT |
| B) EXTERIOR DOORS |
| C) MULLIONS |
| D) ROOF ASSEMBLIES |
| |
| 11) 1606.4.4 ANCHOR METHODS. PROVIDE |
| INFORMATION FOR INSTALLATION OF DOOR |
| AND WINDOW BUCKS. |
| |
| 12) 1707.4.4.1 ANCHOR REQUIREMENTS: |
| WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR |
| ED IN ACCORDANCE WITH THE PUBLISHED |
| MANUFACTURER'S RECOMMENDATIONS TO |
| ACHIEVE THEDESIGN PRESSURE SPECIFIED. |
| SUBSTITUTE ANCHORING SYSTEM USED FOR |
| THE SUBSTRATE NOT SPECIFIED BY THE |
| FENESTRATION MANUFACTURER SHALL PROVIDE |
| EQUAL OR GREATER ANCHORING AS DEMONSTRA- |
| TED BY ACCEPTED ENGINEERING PRACTICES. |
| |
| 1707.4.4.2 WINDOW BUCKS TO BE A MINIMUM |
| 1 1/2" OR WINDOWS SHALL BE FASTENED TO |
| THE STRUCTURAL SUBSTRATE. |
| |
| 13) 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 14) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 15) STRUCTURAL PAGES INDICATE FOR ROOF |
| SHEATHING SEE NOTES ON S-9. NOTE WOOD |
| 6-E INDICATES TO COMPLY WITH 2322.2 |
| WHICH IS FOR HIGH WIND REGIONS, DADE & |
| BROWARD COUNTIES. |
| SEE PALM BEACH COUNTY AMENDMENTS |
| TABLE 2306.1 FOR FASTENING SCHEDULE. |
| SEE "LOCAL CONDITIONS"AND FISCAL IMPACT |
| FOLLOWING TABLE 2309.3A. |
| THE NAILING SCHEDULE IS GOOD FOR |
| HEIGHTS TO 35', ABOVE THIS THE ENGINEER |
| OF RECORD SHALL INDICATE THE NAILING |
| SCHEDULE. THE BEAM OF THE BELL TOWER IS |
| AT 37'-8",ROOF SHEATHING ABOVE. |
| |
| 16)1503.4.2 OVERFLOW DRAINS SHALL BE |
| THE SAME SIZE AS ROOF DRAINS, INSTALLED |
| WITH THE INLET FLOW LINE LOCATED 2" |
| ABOVE THE LOWEST POINT OF THE ROOF LINE. |
| OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| 4"IN HEIGTH AND SHALL BE PLACED IN WALLS |
| OR PARARETS WITH THE INLET FLOW LINE |
| NOT LESS THAN 2" ABOVE THE ROOF SURFACE. |
| |
| 17) 1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 18)1511.7 ROOF MOUNTED MECHANICAL UNIT |
| S SHALL BE MOUNTED ON CURBS RAISED A |
| MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| FACE, OR WHERE ROOFING MATERIALS EXTEND |
| BENEATH THE UNIT, ON RAISED EQUIPMENT |
| SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| HEIGTH IN ACCORDANCE WITH TABLE 1511.7. |
| |
| 19) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| SHEET A-6.4 VS S-2, BELL TOWER, |
| SHEET S-2 BELL TOWER DETAIL INDICATES A |
| BEAM TB-7 @ ELEVATION +20'-0". THE A-6.4 |
| INDICATES A BEAM @ 29"-0" NOT MENTIONED |
| IN STRUCTURAL BEAM SCHEDULE. THIS SEC- |
| TION IS NOT CLEAR 10/S-5, IS THIS INDICA |
| TING RB-12 AND TRUSSES, IS SECTION SHOW- |
| ING TRUSSES CANTILEVERED OVER A BEAM @ |
| ELE. 129'? |
| STRUCTURAL DETAIL, A CUT SECTION LABEL- |
| ING ALL BEAMS & COL. WITH ELE. WOULD BE |
| HELPFUL. |
| |
| THE STRUCTURAL DETAIL AND ARCHITECTURAL |
| DETAILS DO NOT MATCH, A-6.4 INDICATES |
| CONCRETE BEAM BELL TOWER SUPPORTED BY |
| 4X8 WOOD BEAM??????????? |
| |
| BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |