 BUILDING PLAN REVIEW
 PERMIT: 02091306
 ADD: 3600 AUSTRALIAN AVE
 CONT: HEDRICK BROTHERS
 TEL: (561)242-4303
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SUBMIT SOILS REPORT WITH THE MINIMUM
 SAFE BEARING CAPACITY.
  
 3) THE PLANS DO NOT INDICATE THE USE OF
 FIRE SPRINKLERS, FBC 903.7.2.4 REQUIRES
 ASSEMBLY OCC WITH AN OCCUPANCY LOAD
 GREATER THAN 300 PERSONS TO HAVE FIRE
 SPRINKLER PROTECTION. SEE EXCEPTIONS!
  
 4) FBC 10.19.10.1.4. ASSEMBLY OCCUPANCY
 > 200 PERSONS REQUIRE SEATS TO BE FAST-
 ENED TO THE FLOOR.
  
 5) 1019.7.2. FBC ASSEMBLY OCCUPANCY,EACH
 DOOR IN A MEANS OF EGRESS FROM AN AREA
 OF GROUP A OCC. REQUIRES PANIC HARDWARE
 OR FIRE EXIT HARDWARE.
  
 6) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 7)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 WILL THE BLDG BE USED FOR ANYTHING OTHER
 THAN RELIGIOUS SERVICES? THIS MAY ENACT
 OTHER CODE SECTIONS? FL ACCESSIBILITY
  
 8)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 9)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 10)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) WINDOWS, FIXED OR CASEMENT
 B) EXTERIOR DOORS
 C) MULLIONS
 D) ROOF ASSEMBLIES
  
 11) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 12) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 1707.4.4.2 WINDOW BUCKS TO BE A MINIMUM
 1 1/2" OR WINDOWS SHALL BE FASTENED TO
 THE STRUCTURAL SUBSTRATE.
  
 13) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 14) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 15) STRUCTURAL PAGES INDICATE FOR ROOF
 SHEATHING SEE NOTES ON S-9. NOTE WOOD
 6-E INDICATES TO COMPLY WITH 2322.2
 WHICH IS FOR HIGH WIND REGIONS, DADE &
 BROWARD COUNTIES.
 SEE PALM BEACH COUNTY AMENDMENTS
 TABLE 2306.1 FOR FASTENING SCHEDULE.
 SEE "LOCAL CONDITIONS"AND FISCAL IMPACT
 FOLLOWING TABLE 2309.3A.
 THE NAILING SCHEDULE IS GOOD FOR
 HEIGHTS TO 35', ABOVE THIS THE ENGINEER
 OF RECORD SHALL INDICATE THE NAILING
 SCHEDULE. THE BEAM OF THE BELL TOWER IS
 AT 37'-8",ROOF SHEATHING ABOVE.
  
 16)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 17) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 18)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 19) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-6.4 VS S-2, BELL TOWER,
 SHEET S-2 BELL TOWER DETAIL INDICATES A
 BEAM TB-7 @ ELEVATION +20'-0". THE A-6.4
 INDICATES A BEAM @ 29"-0" NOT MENTIONED
 IN STRUCTURAL BEAM SCHEDULE. THIS SEC-
 TION IS NOT CLEAR 10/S-5, IS THIS INDICA
 TING RB-12 AND TRUSSES, IS SECTION SHOW-
 ING TRUSSES CANTILEVERED OVER A BEAM @
 ELE. 129'?
 STRUCTURAL DETAIL, A CUT SECTION LABEL-
 ING ALL BEAMS & COL. WITH ELE. WOULD BE
 HELPFUL.
  
 THE STRUCTURAL DETAIL AND ARCHITECTURAL
 DETAILS DO NOT MATCH, A-6.4 INDICATES
 CONCRETE BEAM BELL TOWER SUPPORTED BY
 4X8 WOOD BEAM???????????
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW