2002-10-23 00:00:00 | THE BUILDING DATA INFORMATION ON SHEET |
| SP-1 IS NOT CLEAR.THE FLOOR AREAS |
| CITED DO NOT AGREE WITH FBC TABLE 500 |
| FOR TYPE IV CONSTRUCTION.WILL THE |
| BUILDING BE FIRE SPRINKLERED?THE FIRE |
| SPRINKLER PLANS NOTED ON THE COVER |
| SHEET ARE NOT INCLUDED WITH THESE PLANS. |
| |
| THIS PLAN REVIEW ASSUMES A TYPE IV FIRE |
| SPRINKLERED BUILDING WAS INTENDED. |
| |
| SHOW THE METHOD OF VENTILATION FOR THE |
| REPAIR GARAGE IN ACCORDANCE WITH FBC |
| 411.5.5. |
| |
| THE AREAS SHOWN AS "DELIVERY" AND |
| "SERVICE" CANOPIES ARE BUILDING AREA |
| AND NOT CANOPIES AS PROVIDED FOR IN FBC |
| 3106.2. (>15' PROJECTION)AS SUCH THEY |
| ARE SUBJECT TO SPRINKLER REQUIREMENTS |
| AND TABLE 600, PARTICULARLY THE WEST |
| ELEVATION.PLEASE REVISE AS NECESSARY. |
| |
| ON CONSTRUCTION OF THIS NATURE, (TILT |
| SLAB), THE BUILDING OFFICIAL WILL |
| REQUIRE A RESIDENT INSPECTOR.CONTACT |
| DON NEELY AT 561-659-8096 X 8333 FOR |
| MORE INFORMATION. |
| |
| BEFORE A PERMIT TO CONSTRUCT MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO THE |
| COUNTY, THE PERMIT PLANS STAMPED BY |
| THAT OFFICE AND A COPY OF THE PAID |
| RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION.CALL 561-233-5025 FOR |
| MORE INFORMATION. |
| |
| IF PRODUCT TEST REPORTS FOR THE DOORS, |
| WINDOWS AND ROOF COVERING ARE NOT |
| INCLUDED WITH THIS PERMIT APPLICATION, |
| A SEPARATE PERMIT AND FEES WILL BE |
| REQUIERED FOR THAT PORTION OF THE WORK. |
| |
| SHOW HOW THE GLAZED PORTIONS OF THE |
| EXTERIOR ENVELOPE WILL RESIST HURRICANE |
| MISSILE IMPACT.SEE FBC 1606.1.4. |