Plan Review Notes
Plan Review Notes For Permit 02091195
Permit Number 02091195
Review Stop B
Sequence Number 1
Notes
Date Text
2002-10-23 00:00:00THE BUILDING DATA INFORMATION ON SHEET
 SP-1 IS NOT CLEAR.THE FLOOR AREAS
 CITED DO NOT AGREE WITH FBC TABLE 500
 FOR TYPE IV CONSTRUCTION.WILL THE
 BUILDING BE FIRE SPRINKLERED?THE FIRE
 SPRINKLER PLANS NOTED ON THE COVER
 SHEET ARE NOT INCLUDED WITH THESE PLANS.
  
 THIS PLAN REVIEW ASSUMES A TYPE IV FIRE
 SPRINKLERED BUILDING WAS INTENDED.
  
 SHOW THE METHOD OF VENTILATION FOR THE
 REPAIR GARAGE IN ACCORDANCE WITH FBC
 411.5.5.
  
 THE AREAS SHOWN AS "DELIVERY" AND
 "SERVICE" CANOPIES ARE BUILDING AREA
 AND NOT CANOPIES AS PROVIDED FOR IN FBC
 3106.2. (>15' PROJECTION)AS SUCH THEY
 ARE SUBJECT TO SPRINKLER REQUIREMENTS
 AND TABLE 600, PARTICULARLY THE WEST
 ELEVATION.PLEASE REVISE AS NECESSARY.
  
 ON CONSTRUCTION OF THIS NATURE, (TILT
 SLAB), THE BUILDING OFFICIAL WILL
 REQUIRE A RESIDENT INSPECTOR.CONTACT
 DON NEELY AT 561-659-8096 X 8333 FOR
 MORE INFORMATION.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 IF PRODUCT TEST REPORTS FOR THE DOORS,
 WINDOWS AND ROOF COVERING ARE NOT
 INCLUDED WITH THIS PERMIT APPLICATION,
 A SEPARATE PERMIT AND FEES WILL BE
 REQUIERED FOR THAT PORTION OF THE WORK.
  
 SHOW HOW THE GLAZED PORTIONS OF THE
 EXTERIOR ENVELOPE WILL RESIST HURRICANE
 MISSILE IMPACT.SEE FBC 1606.1.4.