Plan Review Notes For Permit 02090784 |
Permit Number |
02090784 |
|
Review Stop |
FS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-10-01 00:00:00 | SINCE A SINGLE FIRE SPRINKLER SYSTEM | | WILL BE PROTECTING BOTH BUILDINGS IT | | IS CRITICAL THAT THE AREA OF PROTECTION | | NOT BE EXCEEDED. PLEASE INDICATE WHAT | | THE TOTAL AREA BEING PROTECTED FOR BOTH | | BUILDINGS WILL BE AS IT RELATES TO A | | SINGLE SUPPLY AND RISER SYSTEM. | | | | NO INDICATION OF ANY ALARM VALVE. | | | | NO INDICATION OF ANY SPARE SPRINKLER | | HEADS OR WRENCH PLANNED FOR THE NEW | | INSTALLATION. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|