2002-09-17 00:00:001) SINCE THE BUILDING IS NOT FIRE
 SPRINKLER PROTECTED, DEAD-END CORRIDORS
 ARE NOT PERMITTED OVER TWENTY (20) FEET
 IN LENGTH.
  
 2) SINCE THE BUILDING IS NOT FIRE
 SPRINKLER PROTECTED, ALL ELECTRICAL,
 MECHANICAL, AND STORAGE ROOMS ARE TO BE
 FIRE SEPARATED BY AT LEAST ONE HOUR
 WITH OPENING PROTECTIVES.
  
 3) FIRE ALARM NOTES # 11 INDICATES
 SECURITY DEVICES TIED INTO FIRE
 ALARM SYSTEM. PLEASE BE ADVISED THAT
 OTHER REQUIREMENTS ARE TO BE MET PRIOR
 TO PLACING SECURITY DEVICES ON EXIT
 DOORS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910