Plan Review Notes For Permit 02090768 |
Permit Number |
02090768 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-09-17 00:00:00 | 1) SINCE THE BUILDING IS NOT FIRE | | SPRINKLER PROTECTED, DEAD-END CORRIDORS | | ARE NOT PERMITTED OVER TWENTY (20) FEET | | IN LENGTH. | | | | 2) SINCE THE BUILDING IS NOT FIRE | | SPRINKLER PROTECTED, ALL ELECTRICAL, | | MECHANICAL, AND STORAGE ROOMS ARE TO BE | | FIRE SEPARATED BY AT LEAST ONE HOUR | | WITH OPENING PROTECTIVES. | | | | 3) FIRE ALARM NOTES # 11 INDICATES | | SECURITY DEVICES TIED INTO FIRE | | ALARM SYSTEM. PLEASE BE ADVISED THAT | | OTHER REQUIREMENTS ARE TO BE MET PRIOR | | TO PLACING SECURITY DEVICES ON EXIT | | DOORS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|