2002-09-18 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARIFY PANELS "A1" AND | | "B" ARE SHOWN AS MLO AND MAIN BRKR? | | | | 2)NOTE: PLEASE NOTE, IT IS NOTED THAT | | ALL LOADS SHOWN ARE AT CONNECTED LOAD. | | PLEASE SHOW CALCS. SQ.FT/ RECEPTS/ | | AND CONTINOUS LOADS AT 125%. | | 220-3,220-10,-220-11,220-13,230-42,215-3 | | | | 3)NOTE: PLEASE CLARIFY EM LTS SHOWN AS | | NEW/RELOCATED AS CONNECTED TO LIGHTING/ | | BRANCH CIRCUIT. PER 700-12E | | | | PLEASE SEE FIRE REVIEW COMMENTS AND | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|