Plan Review Notes For Permit 02090718 |
Permit Number |
02090718 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-04-07 00:00:00 | ************** UNSAT ****************** | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | PLANS AND CORRELATE W/ SUBMITTED PANEL | | SCHEDULE. CIRCUITING FOR EM/EXT LTS | | 700-12E | | 2)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS | | ONLY ONE CIRCUIT FOR OFFICE RECEPTS?? | | 220-13 | | | | 3)NOTE: PLEASE CLARIFY 100/20 SHOWN | | ON PANEL SCHEDULE. | | | | 4)NOTE: PLEASE SEE PANEL SCH. SHOWS A | | 200A 2/P, ? FOR? | | CIRCUIT #4 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | [email protected] |
|