Notes
Date Text
2002-12-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW, PLEASE PROVIDE
 A WATER RISER DIAGRAM.
 2) FROM PREVIOUS REVIEW, PLEASE PROVIDE
 A DETAIL FOR THE DRINKING FOUNTAIN. SHOW
 COMPLIANCE WITH 11-4.15 AND ALL SUBSECT-
 IONS. ALSO SHOW PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING PER
 11-4.1.3(10)(A).
 3) FROM PREVIOUS REVIEW, PLEASE SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS AND SHOW LOCATIONS FOR EACH.
 SEE SECTIONS 1106 & 1107.ALSO ADD 1/2
 AREA FOR ALL VERTICAL WALLS.
 4) FROM PREVIOUS REVIEW, PLEASE INDICATE
 TYPE OF MATERIAL TO BE STORED ON SECOND
 FLOOR. OTHER REVIEW COMMENTS MAY RESULT
 ACCORDING TO INFORMATION GIVEN.
 5) COMMENTS BY BLDG AND FIRE REVIEWS
 WERE ANSWERED IN WRITTEN FORM, BUT NOT
 FOR PLUMBING. PLEASE INDICATE WHERE AND
 HOW COMMENTS ARE ADDRESSED FOR TIMELY
 REVIEW.
  
 REVIEW BY KEN STEVENS